Ratings

A

S

M

E

H

Notes:

1. As an Energy Star Partner, Lochinvar has determined that

outdoor boilers meet the Energy Star guidelines for energy
efficiency.

2. The ratings are based on standard test procedures prescribed

by the United States Department of Energy.

3. Net AHRI ratings are based on net installed radiation of

sufficient quantity for the requirements of the building
and nothing need be added for normal piping and pickup.
Ratings are based on a piping and pickup allowance of 1.15.

4. Standard outdoor boilers are equipped to operate from sea

level to 4,500 feet only with no adjustments. The boiler will
de-rate by 4% for each 1,000 feet above sea level up to 4,500
feet.

5. Ratings have been confirmed by the Hydronics Section of

AHRI.

6. Outdoor boilers temperature controls comply with the

requirements of CSD-1 Section CW-400 requirements.

The manual reset high limit provided with the outdoor
boiler is listed to UL353.

Maximum allowed working pressure is located on the rating plate.

NOTICE

Outdoor Knight Boiler

AHRI Rating

Model Number

Note: Change “N” to

“L” for L.P. gas models.

Input

MBH

(Note 4)

Max Min

Heating

Capacity

MBH

(Note 2,5)

Net

AHRI

Ratings

Water,

MBH

(Note 3,5)

AFUE

%

(Note 1, 5)

OKN151

30

150

141

122

94

OKN211

42

210

197

171

94

OKN286

57

285

266

232

94

Other Specifications

Boiler

Water

Content

Gallons

Water

Connections

Gas

Connections

Air

Size

1.3

1"

1/2"

3"

1.7

1"

1/2"

3"

2.4

1-1/4"

3/4"

4"

Outdoor Knight Boiler Installation & Operation Manual