The Outdoor Knight Boiler - How it works...

1. Stainless steel heat exchanger

Allows system water to flow through specially designed

coils for maximum heat transfer, while providing

protection against flue gas corrosion. The coils are

encased in a jacket that contains the combustion process.

2. Combustion

chamber

access

cover

Allows access to the combustion side of the heat

exchanger

coils.

3. Blower

The blower pulls in air and gas through the venturi (item

5). Air and gas mix inside the blower and are pushed into the

burner, where they burn inside the combustion chamber.

4. Gas

valve

The gas valve senses the negative pressure created by the

blower, allowing gas to flow only if the gas valve is

powered and combustion air is flowing.

5. Venturi

The venturi controls air and gas flow into the burner.

6. Flue gas sensor (limit rated)

This sensor monitors the flue gas exit temperature. The control

module will modulate and shut down the boiler if flue gas

temperature gets too hot. This protects the flue pipe from

overheating.

7. Boiler outlet temperature sensor (housed with the

high limit sensor)

This sensor monitors boiler outlet water temperature (system

supply). If selected as the controlling sensor, the control

module adjusts boiler firing rate so the outlet temperature is

correct.

8. Boiler inlet temperature sensor

This sensor monitors return water temperature (system

return). If selected as the controlling sensor, the control

module adjusts the boiler firing rate so the inlet temperature is

correct.

9. Temperature and pressure gauge (field installed, not
shown)

Monitors the outlet temperature of the boiler as well as the

system water pressure.

10. Electronic LCD display

The electronic display consists of 4 buttons, a navigation dial

and a multiple line liquid crystal display.

11. Flue pipe adapter

Allows for the connection of the vent system to the

boiler.

12. Burner (not shown)

Made with metal fiber and stainless steel construction,

the burner uses pre-mixed air and gas and provides a

wide range of firing rates.

13. Water outlet (system supply)

NPT water connection that supplies hot water to the

system, either 1" or 1-1/4", depending on the
model.

14. Water inlet (system return)

NPT water connection that returns water from the

system to the heat exchanger, either 1" or 1-1/4",

depending on the model.

15. Gas connection pipe

Threaded pipe connection, either 1/2" or 3/4",

depending on the model. This pipe should be connected

to the incoming gas supply for the purpose of delivering

gas to the boiler.

16. SMART SYSTEM Control Module

The SMART SYSTEM Control responds to internal and

external signals and controls the blower, gas valve, and pumps

to meet the heating demand.

17. Manual air vent

Designed to remove trapped air from the heat exchanger

coils.

18. High voltage junction box

The junction box contains the connection points for the line

voltage power and all pumps.

19. Boiler drain port

Location from which the heat exchanger can be drained.

20. Low voltage connection board

The connection board is used to connect external low voltage

devices.

21. Low voltage wiring connections

Conduit connection points for the low voltage
connection

board.

22. Condensate drain connection

Connects the condensate drain line to a 1/2" PVC union.

23. Access cover - top front

Provides protection of the control panel / display from outside

elements.

24. Access cover - bottom front

Provides access to the burner.

25. Ignition electrode

Provides direct spark for igniting the burner.

26. Flame inspection window

The quartz glass window provides a view of the burner

surface and flame.

27. Relief valve

Protects the heat exchanger from an over pressure condition.

The relief valve provided with the unit is set at 30 psi.

28. Flame sensor

Used by the control module to detect the presence of burner

flame.

29. Line voltage wiring connections

Conduit connection points for the high voltage junction box.

30. Top access cover

Provides access to the internal components.

31. Power switch

Turns 120 VAC ON/OFF to the boiler.

32. Leveling legs

Used to allow the heat exchanger to be leveled. This is needed

for the proper draining of the condensate from the combustion

chamber.

33.

Air pressure switch

The air pressure switch detects blocked inlet conditions.

34.

Transformer

The transformer provides 24V power to the integrated control.

35.

High limit sensor (housed with the outlet

temperature

sensor)

Device that monitors the outlet water temperature. If the

temperature exceeds its setting, the integrated control will

break the control circuit, shutting the boiler down.

36. Gas shutoff switch

An electrical switch designed to cut power to the gas valve to

prevent releasing any gas.

37. Over-temp switch (Model 286 Only) (located underneath
access

cover)

An electrical switch designed to shut down boiler operation in

the event the outer back of the heat exchanger, directly above the

flue connection exceeds 604°F (318°C). This is a one time

switch and could warrant a heat exchanger replacement. Check

the integrity of the rear refractory at the back of the upper coil if

the switch opens.

38. Air cover

Covers the over-temp switch and the flue collar with flue sensor.

39. Flue pipe assembly

Factory supplied components for a complete venting system.