Hydronic piping – Lochinvar Outdoor Knight Boiler 151-286 User Manual

Page 18

background image

18

3

Hydronic piping

INDIRECT

DHW TANK

BACKFLOW

PREVENTER

PRESSURE

REDUCING VALVE

PRESSURE

GAUGE

ANTI-SCALD

MIXING VALVE

AIR SEPARATOR

EXPANSION

TANK

ZONE #1

ZONE #2 ZONE #3 ZONE #4

BALL VALVE

(TYPICAL)

DRAIN POINT

(TYPICAL)

MAKE UP WATER

ZONE CIRCULATORS

(TYPICAL)

FLOW CHECK

VALVE

(TYPICAL)

NOT TO EXCEED 4 PIPE DIA OR MAX. OF 12" APART

BOILER
CIRCULATOR

BOILER 2

(MEMBER 1)

DOMESTIC

HOT WATER

CIRCULATOR

UNION

(TYPICAL)

HOT

WATER

OUT

COLD

WATER

IN

BOILER 1

(LEADER)

SYSTEM SUPPLY

SENSOR

TEMPERATURE /

PRESSURE

GAUGE

DRAIN

MAY SUBSTITUTE

LOW LOSS HEADER

Y-STRAINER
(RECOMMENDED)
(TYPICAL)

IMG00371

Figure 3-5 Multiple Boilers - Single Temperature Zoned with Circulators

Please note that these illustrations are meant to show system piping concept only, the installer is responsible
for all equipment and detailing required by local codes.

Indoor tank shown for illustration purposes.

NOTICE

Model

Number of Units

2

3

4

5

6

7

8

Required Pipe Sizes

151

2"

2"

2-1/2" 2-1/2"

3"

3"

3-1/2"

211

2"

2-1/2"

3"

3"

3-1/2"

4"

4"

286

2-1/2" 2-1/2"

3"

3-1/2" 3-1/2"

4"

5"

Outdoor Knight Boiler Installation & Operation Manual