Hydronic piping

12. System temperature sensor:
Lochinvar supplies a system temperature sensor.

The sensor is to be installed in the heating loop

downstream from the boiler hot water piping and

heating loop junction. Typically the sensor will be

located far enough downstream to sense system diluted

water

temperature.

13. Indirect water heaters:

The outdoor boiler may be piped to an indirect

water heater to heat domestic hot water with the space heat

transfer medium. As depicted on pages 17 through 23

there are two options when utilizing an indirect water

heater.

A. The space heating piping will branch off to flow the

space heat transfer medium through a single wall

heat exchanger coil inside the indirect water heater.

B. The indirect water heater is connected to the system

supply piping. A pump controlled by the

outdoor

boiler’s control will regulate the flow of

water through the indirect water heater. The indirect

water heater’s temperature will be regulated by the

outdoor

boiler’s

control.

The outdoor boiler is pre-configured to control the
operation of the DHW pump with Domestic Hot Water
Prioritization programming. The DHW programming is
designed to control and balance the space heating
demand by switching between DHW and space heating.

ƽ WARNING The National Standard Plumbing Code

and the Uniform Plumbing Code limit the
pressure of the heat transfer fluid to less
than the minimum working pressure of the
potable water system up to 30 psi maximum.
Also, the heat transfer fluid must be water
or other non-toxic fluid having a toxicity of
Class 1, as listed in Clinical Toxicology of
Commercial Products, 5

th

Edition.

14. Y-Strainer:

Field supplied. A Y-strainer or equivalent multipurpose

strainer is recommended at the inlet of the heat exchanger

to remove system particles from older hydronic systems and

protect newer systems.

CAUTION

It is up to the installer to ensure the
minimum system flow is not less than the
minimum boiler flow at any time.

Circulator sizing

The outdoor boiler heat exchanger does have a pressure drop,
which must be considered in your system design. Refer to the
graph in FIG. 3-3 for pressure drop through the outdoor boiler
heat exchanger.

INDIRECT

DOMESTIC

HOT WATER

TANK

TO FLOOR

DRAIN

DOMESTIC HOT
WATER PUMP

BOILER
PUMP

SYSTEM
PUMP

Y-STRAINER

(RECOMMENDED)

DRAIN
(TYPICAL)

TO SYSTEM

FROM SYSTEM

FROM

TO

IMG00377

Figure 3-2A Near Boiler Piping w/Y-Strainer

Y-STRAINER

(RECOMMENDED)

FILL VALVE

EXPANSION TANK

DRAIN VALVE

SYSTEM SENSOR

AIR SEPARATOR

LOW LOSS HEADER

(TYPICAL)

AIR VENT VALVE

DRAIN
(TYPICAL)

TO

SY

ST

EM

FR

OM

SY

ST

EM

FR

OM

TO

INDIRECT

DOMESTIC

HOT WATER

TO FLOOR
DRAIN

BOLIER PUMP

IMG00378

Figure 3-2B Near Boiler Piping w/Low Loss Header

Near boiler piping connections

Outdoor Knight Boiler Installation & Operation Manual

Lochinvar offers the Squire which is a series of indirect
water heaters. The Squire features a stainless steel vessel
with a single wall stainless steel heat exchanger.