Hydronic piping – Lochinvar Outdoor Knight Boiler 151-286 User Manual

Page 13

background image

13

*See the piping illustrations included in this section, FIG.’s 3-4
thru 3-10 for suggested guidelines in piping the outdoor boiler
with either zone valves or circulator pumps.

*Please note that these illustrations are
meant to show system piping concept only,
the installer is responsible for all equipment
and detailing required by local codes.

NOTICE

ƽ WARNING

The relief valve, tee and any necessary fittings
are shipped in the install kit with the boiler
and are to be field installed (FIG. 3-1).

CAUTION

The outdoor boiler is capable of servicing
multiple temperature loop systems. It is the
responsibility of the installer to protect the
loops with lower temperature requirements
from higher temperatures that may be
required by other loops.

Relief valve and temperature and pressure

gauge installation

Basic steps are listed below to guide you through the installation
of the relief valve and the temperature and pressure (T & P)
gauge provided with the unit.
1. Install the tee with the 3/4 inch fitting positioned

vertically and on the top as shown in FIG. 3-1.

2. Install the relief valve into the 3/4 inch fitting of the tee

installed in Step 1 (FIG. 3-1).

3. Install a field provided 5 inch long nipple and tee with the
fitting positioned vertically on the top on the

downstream side of the relief valve (see FIG. 3-1).

4. Install the temperature and pressure gauge provided with

the unit into the top fitting of the tee (a bushing may be

necessary) installed in Step 3 (FIG. 3-1).

3

Hydronic piping

(continued)

IMG00369

RELIEF VALVE

TEMPERATURE &
PRESSURE GAUGE

TEE W/FITTING ON TOP
(FIELD PROVIDED)

CLOSE NIPPLE
(FIELD PROVIDED)

TEE WITH 3/4" FITTING
ON TOP

CLOSE NIPPLE

Figure 3-1 Relief Valve / T & P Installation

Near boiler piping components

1. Boiler system piping:

Boiler system piping MUST be sized per the pipe

requirements listed in Table 3A. Reducing the pipe size

can restrict the flow rate through the boiler, causing

inadvertent high limit shutdowns and poor system

performance. Flow rates are based on 20 feet of piping,

4 - 90° elbows, and 2 - fully ported ball valves.

2. Boiler system pump w/pump cover:

A Grundfos UPS26-99F pump and pump cover will be

provided by the factory (for standard altitude models) as

the boiler circulation pump based on 20 feet of piping,

4 - 90° elbows, and 2 - fully ported ball valves.

Outdoor boilers are capable of controlling a

variable speed boiler circulator. Variable speed circulators

MUST be sized to meet the specified minimum flow

requirements listed in FIG. 3-3 on page 15 at full

speed.
3. Domestic hot water circulating pump:

Field supplied. The pump MUST be sized to meet

the specified minimum flow requirements listed in

FIG. 3-3. Consult the indirect water heater operating

guide to determine flow characteristics for the selected

product

used.

4. Boiler

isolation

valves:

Field supplied. Full port ball valves are required.

Failure to use full port ball valves could result in a

restricted flow rate through the boiler.

5. Check

valves:

Field supplied. Check valves are recommended for

installation as shown in FIG.’s 3-4 thru 3-10. Failure to

install check valves could result in a reverse flow

condition during pump(s) off cycle.

6. Domestic indirect hot water isolation valves:

Field supplied. Full port ball valves are required. Failure

to use full port ball valves could result in a restricted flow

rate through the boiler.

7. Anti-scald mixing valve:
Field supplied. An anti-scald mixing valve is

recommended when storing domestic hot water above

115°F.
8. Unions:

Field supplied. Recommended for unit serviceability.

9. Temperature and pressure gauge:

Factory supplied. The temperature and pressure gauge is

shipped loose. It is the responsibility of the contractor to

install the temperature and pressure gauge on the boiler

water

outlet.

10. Pressure relief valve:

Factory supplied. The pressure relief valve is sized to

ASME

specifications.

11. Boiler purge valve:

Field supplied. The boiler purge valve is used to

remove entrapped air from the heat exchanger during

start-up.

Outdoor Knight Boiler Installation & Operation Manual