beautypg.com

Operating information – Lochinvar Outdoor Knight Boiler 151-286 User Manual

Page 44

background image

44

8

Operating information

Sequence of operation

(continued)

OPERATION

DISPLAY

8. If the space heating call for heat is active, and the tank thermostat

or sensor starts a DHW call for heat, the boiler will switch to the
DHW mode. If programmed for normal DHW operation (not as a
zone), the DHW pump will turn on first, then the boiler pump will
turn off 2 seconds later. This will divert the boiler’s outlet water
from the heating system and send it to the tank coil instead. The
control will then modulate to maintain the outlet temperature to
the DHW boiler set point.

9. If the boiler is not part of a Cascade, and both the space heating

and DHW calls for heat remain active long enough, the boiler will
switch back and forth between the two heating modes until one of
them is satisfied.

10. Once both calls for heat are satisfied, the control will turn off the

burner. The blower will continue to run during the

postpurge period.

11. Any pumps that are running will continue to run for their respective

pump delay times before turning off, unless programmed to
remain on continuously. A 60 second anti-cycle period will start,
which will delay any new call for heat until it times out.

12. In Standby, ready to start a new cycle.

Outdoor Knight Boiler Installation & Operation Manual