beautypg.com

Hydronic piping – Lochinvar Outdoor Knight Boiler 151-286 User Manual

Page 20

background image

20

DOMESTIC

HOT WATER

CIRCULATOR

ANTI-SCALD

MIXING

VALVE

COLD
WATER
IN

AIR SEPARATOR

BALL VALVE

(TYPICAL)

DRAIN POINT

(TYPICAL)

MAKE

UP

WATER

HOT

WATER

OUT

BOILER
CIRCULATOR

BACKFLOW

PREVENTER

PRESSURE
REDUCING VALVE

PRESSURE

GAUGE

EXPANSION

TANK

MIXING VALVES

(TYPICAL)

FLOW CHECK

VALVE

SYSTEM

SUPPLY
SENSOR

MAY SUBSTITUTE
LOW LOSS HEADER

TEMPERATURE

LOOP #1

TEMPERATURE

LOOP #2

TEMPERATURE

LOOP #3

BOILER

INDIRECT

DHW TANK

TEMPERATURE /

PRESSURE

GAUGE

UNION
(TYPICAL)

DRAIN

Y-STRAINER
(RECOMMENDED)

NOT TO EXCEED 4 PIPE DIA OR MAX. OF 12" APART

BOILER

IMG00373

120VAC TO PUMPS

WIRES TO

LOOP

SENSORS

SHIELDED CABLE TO
BOILER CONTROL

MULTI-TEMP

LOOP CONTROL

(OPTIONAL)

24V
SIGNAL
TO MIXING
VALVES

Figure 3-7 Multiple Boilers - Multiple Temperatures

Model

Number of Units

2

3

4

5

6

7

8

Required Pipe Sizes

151

2"

2"

2-1/2" 2-1/2"

3"

3"

3-1/2"

211

2"

2-1/2"

3"

3"

3-1/2"

4"

4"

286

2-1/2" 2-1/2"

3"

3-1/2" 3-1/2"

4"

5"

Please note that these illustrations are meant to show system piping concept only, the installer is responsible
for all equipment and detailing required by local codes.

Indoor tank shown for illustration purposes.

NOTICE

3

Hydronic piping

CAUTION

Mixing valves are required for the protection of low temperature loops.

Outdoor Knight Boiler Installation & Operation Manual