Maintenance maintenance and annual startup, Service technician, Owner maintenance – Lochinvar Outdoor Knight Boiler 151-286 User Manual
Page 49
9
Maintenance
Maintenance and annual startup
Table 9A Service and Maintenance Schedules
Service technician
(see the following pages for instructions)
General:
• Address reported problems
• Inspect interior; clean and vacuum if
necessary;
• Clean condensate trap and fill with fresh
water
•
Check for leaks (water, gas, flue,
condensate)
• Verify flue and air openings in good
condition and free of obstruction
• Check system water pressure/system
piping/expansion
tank
• Check control settings
•
Check ignition and flame sense
electrodes (sand off any deposits; clean
and
reposition)
• Check wiring and connections
•
Perform start-up checkout and
performance verification per Section 7
of this manual.
• Flame inspection (stable, uniform)
• Flame signal (at least 10 microamps at
high fire)
•
Clean the heat exchanger if flue
temperature is more than 54°F above
return water temperature.
If combustion or performance
indicate need:
• Clean heat exchanger
•
Remove and clean burner using
compressed air only
• Clean the blower wheel
ANNUAL START-UP
Owner maintenance
(see the Outdoor Knight User’s Information Manual
for instructions)
Daily
• Check boiler area
•
Check pressure / temperature
gauge
Monthly
• Check air and vent termination
screens
• Check relief valve
• Check condensate drain system
Periodically
• Test low water cutoff (if used)
• Reset button (low water cutoff)
Every
6 months
• Check boiler piping (gas and
water) for leaks
• Operate relief valve
End
of season
months
• Shut boiler down (unless boiler
used for domestic hot water)
49
Outdoor Knight Boiler Installation & Operation Manual