For 208/230/440 voltage machines, see figure a.4, Installation – Lincoln Electric IDEALARC CV-300 User Manual
Page 12
A-5
INSTALLATION
IDEALARC CV-300
A-5
FIGURE A.4 - Reconnect Diagram For 208/230/440 voltage machines.
1.
Check nuts on terminal board for tight-
ness, then place the copper links in the
positions shown. Double up the links in
two of the positions to save them for
future use. Secure the links tightly with
the hex nuts provided. Secure the
remaining hex nuts in place for future
use.
2.
Connect L1, L2, & L3 as shown.
3.
Connect terminal marked to ground ter-
minal per National Electrical Code.
1.
Check nuts on terminal board for tight-
ness, then place the copper links in the
positions shown. Secure the links tight-
ly with the hex nuts provided.
2.
Connect L1, L2, & L3 as shown.
3.
Connect terminal marked to ground
terminal per National Electrical Code.
1.
Check nuts on terminal board for tight-
ness, then place the copper links in the
positions shown. Secure the links tightly
with the hex nuts provided.
2.
Connect L1, L2, & L3 as shown.
3.
Connect terminal marked to ground
terminal per National Electrical Code.
L3
L2
L1
GROUND
INPUT LINES
CONNECTION FOR
460 VOLTS 60HZ.
u
v
w
L3
L2
L1
GROUND
INPUT LINES
CONNECTION FOR
230 VOLTS 60HZ.
u
v
w
L3
L2
L1
GROUND
INPUT LINES
CONNECTION FOR
208 VOLTS 60HZ.
u
v
w