Siemens Schweiz AG
User Manual OEM
CE1U2353en01a
HVAC Products
Overview of OEM settings 22.
November
2006
Operating line
User level
Function
Default value
Minimum
Max
Unit
1630 I
Charging priority
Absolute ¦ Shifting ¦ None ¦ MC shifting, PC absolute
MC shifting, PC absolute
-
1640 F Legionella
function
Off ¦ Periodically ¦ Fixed weekday
Fixed weekday
-
1641 F Legionella funct periodically
3
1
7
Days
1642 F Legionella funct weekday
Monday ¦ Tuesday ¦ Wednesday ¦ Thursday ¦ Friday ¦
Saturday ¦ Sunday
Montag
1644 F Legionella funct time
− − −
− − − / 00:00
23:50
hh:mm
1645 F Legionella funct setpoint
65
55
95
°C
1646 F Legionella funct duration
30
− − − / 10
360
min
1647 F Legionella funct circ pump
Off ¦ On
On
-
1660 F Release of the circulating pump
Time program 3/HCP ¦ DHW release ¦ Time program
4/DHW
DHW release
-
1661 F Circulating pump cycling
Off ¦ On
On
-
1663 F Circulaton
setpoint
45
8
80
°C
Pump H1/H2
2008 O H1 DHW charging priority
No ¦ Yes
Yes
2010 F H1 Excess heat draw
Off ¦ On
On
2014 F H1 prim contr/system pump
No ¦ Yes
Yes
-
2033 O H2 DHW charging priority
No ¦ Yes
Yes
2035 F H2 Excess heat draw
Off ¦ On
On
2039 F H2 prim contr/system pump
No ¦ Yes
Yes
-
Primary controller / system pump
2110 O Flow temp setpoint min
8
8
95
°C
2111 O Flow temp setpoint max
80
8
95
°C
2130 O Mixing valve boost
10
0
50
°C
2132 O Actuator:type
2-position ¦ 3-position
3-position
2133 O Switching differential 2-pos
2
0
20
°C
2134 O Actuator:
running
time
120
30
873
°C
2135 O Mixing
valve
Xp
32
1
100
°C
2136 O Mixing valve Tn
120
10
873
°C
Solar
3810 F Temp diff on
8
BZ 3811
40
°C
3811 F Temp diff off
4
0
BZ 3812
°C
3812 F Charg temp min DHW st tank
− − −
− − − / 8
95
°C
3830 F Collector start function
− − −
− − − / 5
60
min
3831 F Min run time collector pump
60
5
120
s
3840 F Collector frost protection
− − −
− − − / -20
5
°C
3850 F Collector overtemp prot
− − −
− − − / 30
200
°C
3860 F Evaporation heat carrier
− − −
− − − / 60
200
°C