beautypg.com

Siemens Albatros Zone Controler CE1U2353en01a User Manual

Page 6

background image

6/26

Siemens Schweiz AG

User Manual OEM

CE1U2353en01a

HVAC Products

Overview of OEM settings 22.

November

2006

Operating line

User level

Function

Default value

Minimum

Max

Unit

576

E Default

values

No ¦ Yes

No

-

Holidays heating circuit 1
641 E Preselection

Period 1 ¦ Period 2 ¦ Period 3¦ Period 4¦ Period 5¦ Period
6¦ Period 7¦ Period 8

Periode 1

-

642 E Start --.--

01.01

31.12

dd.mm

643 E End --.--

01.01

31.12

dd.mm

648

E Operating level

Frost protection ¦ Reduced

Frost protection

-

Holidays heating circuit 2
651 E Preselection

Period 1 ¦ Period 2 ¦ Period 3¦ Period 4¦ Period 5¦ Period
6¦ Period 7¦ Period 8

Periode 1

-

652 E Start --.--

01.01

31.12

dd.mm

653 E End --.--

01.01

31.12

dd.mm

658

E Operating level

Frost protection ¦ Reduced

Frost protection

-

Holidays heating circuit P
661 E Preselection

Period 1 ¦ Period 2 ¦ Period 3¦ Period 4¦ Period 5¦ Period
6¦ Period 7¦ Period 8

Periode 1

-

662 E Start --.--

01.01

31.12

dd.mm

663 E End --.--

01.01

31.12

dd.mm

668

E Operating level

Frost protection ¦ Reduced

Frost protection

-

Heating circuit 1
710 E Comfort cooling setpoint

20.0

BZ 712

BZ 716

°C

712 E Reduced setpoint

16

BZ 714

BZ 710

°C

714 E Frost protection setpoint

10.0

4

BZ 712

°C

716

F Comfort setpoint max

35.0

BZ 710

35

°C

720 E Heating

curve

slope

1.50

0.10

4.00

-

721 F Heating

curve

displacement

0.0

-4.5

4.5

°C

726 F Heating

curve

adaption

Off ¦ On

Off

-

730 E Summer/winter

heating

limit

18

− − − / 8

30

°C

732

F 24-hour heating limit

-3

− − − / -10

10

°C

740

I

Flow temp setpoint min

8

8

BZ 741

°C

741

I

Flow temp setpoint max

80

BZ 740

95

°C

750

F Room influence

20

− − − / 0

100

%

760

F Room temp limitation

− − −

− − − / 0.5

4

°C

770 F Boost

heating

5

− − − / 0

20

°C

780 F Quick

setback

Off ¦ Down to reduced setpoint ¦ Down to frost prot
setpoint

Down to reduced setpoint

-

790

F Optimum start control max

0

0

360 min

791

F Optimum stop control max

0

0

360 min

800

F Reduced setp increase start

− − −

− − − / -30

10

°C

801 F Reduced

setp

increase

end

-15

-30 BZ

800

°C

820

F Overtemp prot pump circuit

Off ¦ On

On

-

830

F Mixing valve boost

10

0

50

°C