Siemens Albatros Zone Controler CE1U2353en01a User Manual
Page 6
6/26
Siemens Schweiz AG
User Manual OEM
CE1U2353en01a
HVAC Products
Overview of OEM settings 22.
November
2006
Operating line
User level
Function
Default value
Minimum
Max
Unit
576
E Default
values
No ¦ Yes
No
-
Holidays heating circuit 1
641 E Preselection
Period 1 ¦ Period 2 ¦ Period 3¦ Period 4¦ Period 5¦ Period
6¦ Period 7¦ Period 8
Periode 1
-
642 E Start --.--
01.01
31.12
dd.mm
643 E End --.--
01.01
31.12
dd.mm
648
E Operating level
Frost protection ¦ Reduced
Frost protection
-
Holidays heating circuit 2
651 E Preselection
Period 1 ¦ Period 2 ¦ Period 3¦ Period 4¦ Period 5¦ Period
6¦ Period 7¦ Period 8
Periode 1
-
652 E Start --.--
01.01
31.12
dd.mm
653 E End --.--
01.01
31.12
dd.mm
658
E Operating level
Frost protection ¦ Reduced
Frost protection
-
Holidays heating circuit P
661 E Preselection
Period 1 ¦ Period 2 ¦ Period 3¦ Period 4¦ Period 5¦ Period
6¦ Period 7¦ Period 8
Periode 1
-
662 E Start --.--
01.01
31.12
dd.mm
663 E End --.--
01.01
31.12
dd.mm
668
E Operating level
Frost protection ¦ Reduced
Frost protection
-
Heating circuit 1
710 E Comfort cooling setpoint
20.0
BZ 712
BZ 716
°C
712 E Reduced setpoint
16
BZ 714
BZ 710
°C
714 E Frost protection setpoint
10.0
4
BZ 712
°C
716
F Comfort setpoint max
35.0
BZ 710
35
°C
720 E Heating
curve
slope
1.50
0.10
4.00
-
721 F Heating
curve
displacement
0.0
-4.5
4.5
°C
726 F Heating
curve
adaption
Off ¦ On
Off
-
730 E Summer/winter
heating
limit
18
− − − / 8
30
°C
732
F 24-hour heating limit
-3
− − − / -10
10
°C
740
I
Flow temp setpoint min
8
8
BZ 741
°C
741
I
Flow temp setpoint max
80
BZ 740
95
°C
750
F Room influence
20
− − − / 0
100
%
760
F Room temp limitation
− − −
− − − / 0.5
4
°C
770 F Boost
heating
5
− − − / 0
20
°C
780 F Quick
setback
Off ¦ Down to reduced setpoint ¦ Down to frost prot
setpoint
Down to reduced setpoint
-
790
F Optimum start control max
0
0
360 min
791
F Optimum stop control max
0
0
360 min
800
F Reduced setp increase start
− − −
− − − / -30
10
°C
801 F Reduced
setp
increase
end
-15
-30 BZ
800
°C
820
F Overtemp prot pump circuit
Off ¦ On
On
-
830
F Mixing valve boost
10
0
50
°C