User Manual OEM
CE1U2353en01a
HVAC Products
Overview of OEM settings 22.
November
2006
Operating line
User level
Function
Default value
Minimum
Max
Unit
5950 I Function
input
H1
Optg mode change HCs+DHW ¦ Optg mode changeover
HCs ¦ Optg mode changeover HC1 ¦ Optg mode
changeover HC2 ¦ Optg mode changeover HCP ¦
Error/alarm message ¦ Min flow temp setpoint ¦ Excess
heat discharge
Optg mode change
HCs+DHW
-
5951 I
Contact type H1
NC ¦ NO
NO contact
-
5952 I
Min flow temp setpoint H1
70
8
120
°C
5954 I
Heat request 10V H1
100
5
130
°C
5956 I
Pressure value 3.5V H1
5.0
0.0
10.0
bar
5960 I Function
input
H2
Optg mode change HCs+DHW ¦ Optg mode changeover
HCs ¦ Optg mode changeover HC1 ¦ Optg mode
changeover HC2 ¦ Optg mode changeover HCP ¦ Heat
generation lock ¦ Error/alarm message ¦ Min flow temp
setpoint ¦ Heat request ¦ Pressure measurement
Optg mode change
HCs+DHW
-
5961 I
Contact type H2
NC ¦ NO
NO contact
-
5962 I
Min flow temp setpoint H2
70
8
120
°C
6014 I
Function mixing group 1
Heating circuit ¦ Prim contr/system pump
Heating circuit
-
6020 I
Function extension module 1
None ¦ Multi-functional ¦ Heating circuit ¦ Solar DHW ¦
Prim contr/system pump
No function
-
6021 I
Function extension module 2
None ¦ Multi-functional ¦ Heating circuit ¦ Solar DHW ¦
Prim contr/system pump
No function
-
6097 F Sensor type collector
NTC 10k ¦ Platinum 1000
NTC
6030 I Relay
output
QX21
None ¦ Circulating pump Q4 ¦ El imm heater DHW K6 ¦
Collector pump Q5 ¦ H1 pump Q15 ¦ Alarm output K10 ¦
2nd pump speed HC1 Q21 ¦ 2nd pump speed HC2 Q22
¦ 2nd pump speed HCP Q23 ¦ Heat circuit pump HCP
Q20 ¦ H2 pump ¦ Q18 primary pump Q14
None
-
6031 I Relay
output
QX22
None ¦ Circulating pump Q4 ¦ El imm heater DHW K6 ¦
Collector pump Q5 ¦ H1 pump Q15 ¦ Alarm output K10 ¦
2nd pump speed HC1 Q21 ¦ 2nd pump speed HC2 Q22
¦ 2nd pump speed HCP Q23 ¦ Heat circuit pump HCP
Q20 ¦ H2 pump ¦ Q18 primary pump Q14
None
-
6040 I Sensor
input
Bx21
None ¦ DHW sensor B31 ¦ Collector sensor B6 ¦ DHW
circulation sensor B39
None
-
6041 I Sensor
input
BX22
None ¦ DHW sensor B31 ¦ Collector sensor B6 ¦ DHW
circulation sensor B39
None
-
6097 Sensor type collector
NTC 10k ¦ Platinum 1000
NTC
6098 F Readjustm collector sensor
0
-20
20
°C
6100 F Readjustm outside sensor
0.0
-3.0
3.0
°C
6110 F Time
constant
building
15
0
50
h
6112 O Gradient room model
60
0
300
min/°C
6120 F Frost protection plant
Off ¦ On
On
-
6200 I Saving
sensors
No ¦ Yes
No
-