6 dhw storage tank – Siemens Albatros Zone Controler CE1U2353en01a User Manual
Page 19
19/26
Siemens Schweiz AG
User Manual OEM
CE1U2353en01a
HVAC Products
The settings in detail 22.
November
2006
@
2.6 DHW storage tank
Release
Line no.
Operating line
5010 Charging
Once / day
Several times / day
Selection of charging “Once/day“ or “Several times/day” is active only if DHW release is
set according to the time programs of the heating circuits.
Once / day
Release of DHW charging is given 2.5 hours before the first heat request fom the
heating circuit is received. Then, the reduced DHW setpoint applies for the whole day.
Heizprogramm
TWW-Freigabe
2.5h
Einmal pro Tag
In the case of continuous heating (with no setback periods), release of DHW charging
is given at 0:00. The same rule also applies if the first request for heat from the heating
circuit is received before 02:30. If a request for heat is delivered at midnight, DHW
charging is released after the first setback period, but no earlier than 2.5 hours before
midnight.
Tag 1
Tag 2
Tag 3
Tag 4
TWW-Freigabe
Heizprogramm
0:00
24:00
2.5h
2.5h
2.5h
2.5h
22:00
Several times / day
When selecting “Several times/day“, release of DHW charging is put forward in time by
1 hour against the periods of time the heating circuit calls for heat, and is then
maintained during these periods of time.
Heizprogramm
TWW-Freigabe
1h
1h
Mehrmals pro Tag
Charging control
Line no.
Operating line
5024 Switching
diff
If the DHW temperature is lower than the current setpoint minus the switching
differential set here, DHW charging will be started.
DHW charging will be terminated when the temperature reaches the current setpoint.
Charging
Switching diff
Time program
DHW release
Once per day
Several times per
day
Time program
DHW release
Time program
DHW release
Day 1
Day 2
Day 3
Day 4