Siemens Schweiz AG
User Manual OEM
CE1U2353en01a
HVAC Products
Overview of OEM settings 22.
November
2006
Operating line
User level
Function
Default value
Minimum
Max
Unit
6816 F History
9
-
F
Error code 9
- 0
255
-
6818 F History
10
-
F
Error code 10
- 0
255
-
6820 O Reset
history
No ¦ Yes
No
-
Maintenance/service
7140 E manual
control
Off ¦ On
Off
-
7150 I Simulation
outside
temp
- -50.0
50
°C
7170 I Telephone
customer
service
-
Input/output test
7700 I Relay
test
No test ¦ Everything off ¦ DHW pump Q3 ¦ Heating circuit
pump Q2 ¦ Heat circ mix valve op Y1 ¦ Heat circ mix
valve cl Y2 ¦ Relay output QX1 ¦ Relay output QX21
module 1 ¦ Relay output QX22 module 1 ¦ Relay output
QX23 module 1¦ Relay output QX21 module 2 ¦ Relay
output QX22 module 2 ¦ Relay output QX23module 2
No test
-
7730 I
Outside temp B9
- -50.0
50
°C
7732 I
Flow temp B1
-
0.0
140
°C
7750 I
DHW temp B3
-
0.0
140
°C
7820 I Sensor temp BX1
-
-28.0 350
°C
7821 I Sensor temp BX2
-
-28.0 350
°C
7830 I
Sensor temp BX21 module 1
0
-28
350
°C
7831 I
Sensor temp BX22 module 1
0
-28
350
°C
7832 I
Sensor temp BX21 module 2
0
-28
350
°C
7833 I
Sensor temp BX22 module 2
0
-28
350
°C
7841 I
Contact state H1
Open ¦ Closed
Open
-
7846 I
Contact state H2
Open ¦ Closed
Open
-
Status:
8000 I State
heating
circuit
1
-
-
8001 I State
heating
circuit
2
-
-
8002 I State
heating
circuit
P
-
-
8003 I State
DHW
-
-
8007 I State
solar
-
-
Diagnostics heat source
8510 I
Collector temp 1
-
-28.0
350
°C
8511 I
Collector temp 1 max
0
-28.0
350
°C
8512 I
Collector temp 1 min
0
-28.0
350
°C
8513 I
dT collector 1/DHW
-
-28.0
350
°C
8514 I
dT collector 1/buffer
-
-28.0
350
°C
8530 F Hours run solar yield
-
0
65535
h
8531 F Hours run collect overtemp
-
0
65535
h
Diagnostics consumers
8700 I
Outside temperature
- -50.0
50.0
°C
8703 I
Outside temp attenuated
- -50.0
50.0
°C
8704 I
Composite outside temperature
- -50.0
50.0
°C