The settings in detail 22.
November
2006
2 The settings in detail
2.1 Operator
section
Operation and display
Line no.
Operating line
30 Data:read
No
Yes
31 Data:write
No
Yes
The setting data of all operating levels are copied from the controller to the memory of
the operator unit. This means that previous data in the operator unit will be overwritten.
With the exception of the data listed below, the setting data of all operating levels are
transferred from the memory of the operator unit to the connected controller. Previous
setting data in the controller will be overwritten.
The following data will not be overwritten:
Line no.
Operating line
3
Year
130
Room unit 1
131
Room unit 2
132
Outside sensor
133
Repeater
134
Operator unit
135
Service unit
138
Delete all devices
516
default values
536
default values
556
default values
576
default values
6222 Device
hours
run
6600 device
address
6601 Segment
address
6650 Outside
temp
source
2.2 Heating
circuits
mixing valve control
Line no.
Operating line
HC1 HC2 HC3P
835 1135
Mixing
valve
Xp
836 1136
Mixing
valve
Tn
The proportional band defines within which change of the control variable
∆x (∆T of the
flow) the whole correcting span y (valve travel) is traversed.
The smaller the proportional band, the greater the change of the manipulated variable
∆y at a given change of the controlled variable ∆x.
The integral action time is the period of time the controller’s I-part would require to
produce the same change of the manipulated variable as the P-part
Data:read
Data:write
Mixing valve Xp
Mixing valve Tn