Siemens Albatros Zone Controler CE1U2353en01a User Manual
Page 10
10/26
Siemens Schweiz AG
User Manual OEM
CE1U2353en01a
HVAC Products
Overview of OEM settings 22.
November
2006
Operating line
User level
Function
Default value
Minimum
Max
Unit
DHW storage tank
5010 O Charging
Once/day ¦ Several times/day
Several times / day
5020 F Increase of the flow temperature setpoint
16
0
30
°C
5022 F Type of charging
With B3 ¦ With B3/B31 ¦ With B3, legio B3/B31
With B3/B31
5024 O Switching
diff
5
0
20
°C
5030 O Charging
time
limitation
150
− − − / 10
600
min
5040 O Discharging
protection
Off ¦ Always ¦ Automatically
Automatic
5050 F Charging temp max
80
8
BZ 5051 OEM
°C
5051 O Storage tank temp max
90
8
95
°C
5055 F Recooling
temp
60
8 95 °C
5056 F Recooling heat gen/HCs
Off ¦ On
Off
-
5057 F Recooling
collector
Off ¦ Summer ¦ Always
Off
-
5060 F Electric immersion heater:operating mode
Substitute ¦ Summer ¦ Always
Substitute
-
5061 F Electric immersion heater:release
24h/day ¦ DHW release¦ Time program4/ DHW
DHW release
-
5062 F El
immersion
heater
control
External thermostat ¦ DHW sensor
DHW sensor
-
5070 O Automatic
push
Off ¦ On
On
5085 F Excess heat draw
Off ¦ On
On
-
5092 F With prim contr/system pump
No ¦ Yes
No
5093 F With solar integration
No ¦ Yes
Yes
Configuration
5710 I
Heating circuit 1
Off ¦ On
On
-
5715 I
Heating circuit 2
Off ¦ On
On
-
5730 I
DHW sensor B3
Sensor ¦ Thermostat
Sensors
-
5731 I
DHW controlling element Q3
None ¦ Charging pump ¦ Diverting valve
charging pump
-
5890 I Relay
output
QX1
None ¦ Circulating pump Q4 ¦ El imm heater DHW K6 ¦
Collector pump Q5 ¦ H1 pump Q15 ¦ Alarm output K10 ¦
2nd pump speed HC1 Q21 ¦ 2nd pump speed HC2 Q22
¦ 2nd pump speed HCP Q23 ¦ Heat circuit pump HCP
Q20 ¦ H2 pump ¦ Q18 primary pump Q14
None
-
5930 I Sensor
input
BX1
None ¦ DHW sensor B31 ¦ Collector sensor B6 ¦ DHW
circulation sensor B39
None
-
5931 I Sensor
input
BX2
None ¦ DHW sensor B31 ¦ Collector sensor B6 ¦ DHW
circulation sensor B39
None
-