beautypg.com

4 pump h1/h2, 5 primary controller / system pump – Siemens Albatros Zone Controler CE1U2353en01a User Manual

Page 17

background image

17/26

Siemens Schweiz AG

User Manual OEM

CE1U2353en01a

HVAC Products

The settings in detail 22.

November

2006

Example:

0

6

12

24

5

h

23

77

Z1

6

16 17

Time program 4 / DHW
For DHW heating, time switch program 4 of the local controller is used. The set
switching times of that program are used to switch between the nominal DHW setpoint
and the reduced DHW setpoint. This way, the DHW is heated independently of the
heating circuits.

Example:

2.4 Pump

H1/H2

pump H1

Line no.

Operating line

H1 H2

2008 2033 H1/H2 DHW charging priority

Off ¦ On


When using this setting, the connected pump H1/H2 can be excluded from / included in
the effect of DHW charging priority.
In the case of a ventilation system, for example, it is thus possible to ensure a constant
supply of heat with no impact from DHW charging priority.

2.5 Primary controller / system pump

flow temperature setpoint limitations

Line no.

Operating line

2110

Flow temp setpoint min

2111

Flow temp setpoint max


Using this limitation, a temperature range for the flow temperature setpoint can be
defined. If the requested flow temperature setpoint reaches the relevant limit and the
heat request increases or decreases, the flow temperature setpoint will be maintained
at the maximum or minimum limit.

H1/H2 DHW charging
priority

0

6

12

18

24

h

23

73

Z

2

4