Overview of OEM settings 22.
November
2006
Operating line
User level
Function
Default value
Minimum
Max
Unit
832 F Actuator:type
2-position ¦ 3-position
3-position -
833
F Switching differential 2-pos
2
0
20
°C
834
F Actuator:
running
time
120
30
873
s
835 O
Mixing
valve
Xp
32
1
100
°C
836
O Mixing valve Tn
120
10
873
s
850
I
Floor curing function
Off ¦ Functional heating ¦ Curing heating ¦
Functional/curing heating¦ Manually
Off
-
851
I
Floor curing setp manually
25
0
95
°C
861
F Excess heat draw
Off ¦ Heating mode ¦ Always
Always
872
F With prim contr/system pump
No ¦ Yes
Yes
900 I Optg
mode
changeover
Protection ¦ Recuced
Protection
Heating circuit 2
1010 E Comfort cooling setpoint
20.0
BZ 1012
BZ 1016
°C
1012 E Reduced setpoint
16
BZ 1014
BZ 1010
°C
1014 E Frost protection setpoint
10.0
4
BZ 1012
°C
1016 F Comfort setpoint max
35.0
BZ 1010
35
°C
1020 E Heating curve slope
1.50
0.10
4.00
-
1021 F Heating curve displacement
0.0
-4.5
4.5
°C
1026 F Heating curve adaption
Off ¦ On
Off
-
1030 E Summer/winter heating limit
18
− − − / 8
30
°C
1032 F 24-hour heating limit
-3
− − − / -10
10
°C
1040 I
Flow temp setpoint min
8
8
BZ 1041
°C
1041 I
Flow temp setpoint max
80
BZ 1040
95
°C
1050 F Room influence
20
− − − / 0
100
%
1060 F Room temp limitation
− − −
− − − / 0.5
4
°C
1070 F Boost
heating
5
− − − / 0
20
°C
1080 F Quick setback
Off ¦ Down to reduced setpoint ¦ Down to frost prot
setpoint
Down to reduced setpoint
-
1090 F Optimum start control max
0
0
360 min
1091 F Optimum stop control max
0
0
360 min
1100 F Reduced setp increase start
− − −
− − − / -30
10
°C
1101 F Reduced setp increase end
-15
-30 BZ
1100
°C
1120 F Overtemp prot pump circuit
Off ¦ On
On
-
1130 F Mixing valve boost
10
0
50
°C
1132 F Actuator:type
2-position ¦ 3-position
3-position -
1133 F Switching differential 2-pos
2
0
20
°C
1134 F Actuator:
running
time
120
30
873
s
1135 O Mixing
valve
Xp
32
1
100
°C
1136 O Mixing valve Tn
120
10
873
s
1150 F Floor curing function
Off ¦ Functional heating ¦ Curing heating ¦
Functional/curing heating¦ Manually
Off
-