Siemens Albatros Zone Controler CE1U2353en01a User Manual
Page 8
8/26
Siemens Schweiz AG
User Manual OEM
CE1U2353en01a
HVAC Products
Overview of OEM settings 22.
November
2006
Operating line
User level
Function
Default value
Minimum
Max
Unit
1151 F Floor curing setp manually
25
0
95
°C
1161 F Excess heat draw
Off ¦ Heating mode ¦ Always
Always
1172 F With prim contr/system pump
No ¦ Yes
Yes
1200 I Optg
mode
changeover
Protection ¦ Recuced
Protection
Heating circuit P
1300 E Operating
mode
Protection ¦ Automatic ¦ Reduced ¦ Comfort
Automatic
-
1310 E Comfort cooling setpoint
20.0
BZ 1012
BZ 1016
°C
1312 E Reduced setpoint
16
BZ 1014
BZ 1010
°C
1314 E Frost protection setpoint
10.0
4
BZ 1012
°C
1316 F Comfort setpoint max
35.0
BZ 1010
35
°C
1320 E Heating
curve
slope
1.50 0.10
4.00
-
1321 F Heating
curve
displacement
0.0
-4.5
4.5
°C
1326 F Heating
curve
adaption
Off ¦ On
Off
-
1330 E Summer/winter
heating
limit
18
− − − / 8
30
°C
1332 F 24-hour heating limit
-3
− − − / -10
10
°C
1340 F Flow temp setpoint min
8
8
BZ 1041
°C
1341 F Flow temp setpoint max
80
BZ 1040
95
°C
1350 F Room influence
20
− − − / 0
100
%
1360 F Room temp limitation
− − −
− − − / 0.5
4
°C
1370 F Boost
heating
5
− − − / 0
20
°C
1380 F Quick
setback
Off ¦ Down to reduced setpoint ¦ Down to frost prot
setpoint
Down to reduced setpoint
-
1390 F Optimum start control max
0
0
360 min
1391 F Optimum stop control max
0
0
360 min
1400 F Reduced
setp
increase
start
− − −
− − − / -30
10
°C
1401 F Reduced setp increase end
-15
-30
BZ 1100
°C
1420 F Overtemp prot pump circuit
Off ¦ On
On
-
1450 I
Floor curing function
Off ¦ Functional heating ¦ Curing heating ¦
Functional/curing heating¦ Manually
Off
-
1451 I
Floor curing setp manually
25
0
95
°C
1455 F Floor curing setp current
0
0
95
°C
1456 F Floor curing day current
0
0
32
°C
1461 F Excess heat draw
Off ¦ Heating mode ¦ Always
Always
1172 F With prim contr/system pump
No ¦ Yes
Yes
1500 I Optg
mode
changeover
Protection ¦ Recuced
Protection
Domestic hot water
1610 E Nominal setpoint
55
BZ 1612
BZ 1614 OEM
°C
1612 F Reduced setpoint
40
8
BZ 1610
°C
1614 O Nominal
setpoint
max
65
8
80
°C
1620 I Release
24h/day ¦ Time programs HCs ¦ Time program 4/DHW
Time programs HCs
-