beautypg.com

Siemens rdf600kn User Manual

Operating instructions rdf600kn

background image

CE1B3171.1en / 2012-08-29

Subject to change

Siemens Building Technologies

s

Operating Instructions

RDF600KN

RDF600KN – the room thermostat with KNX communications allows you to set the ideal room temperature.
The thermostat provides Comfort, Economy, and Protection mode and can operate in Auto timer mode using a time
schedule provided via bus.

The fan operates either in Auto mode or at a speed selected in Manual mode.

You can either take advantage of the thermostat's factory settings or adjust it as needed.

Display

Protection

mode

Auto Timer mode

Comfort

mode

Economy

mode


Measured room temperature,
setpoints and parameters

Current time of day or additional
user information

Actual room temperature

Outdoor

temperature

Fault indicator *

Condensation in the room *

Cooling demand / mode

Heating demand / mode
Electric heater active

Extended Comfort mode *

Automatic

fan

Low fan speed

Medium fan speed

High fan speed

Buttons are locked


Weekday 1…7
(1 = Monday / 7 = Sunday)

Operation

an

d settin

gs

Operating mode button

 **  ** 


Notes:

– The thermostat goes back to Auto

Timer mode if a time schedule via
bus changes the operating mode.

– User operations are ignored if a

time schedule via bus sets the
operating mode to protection.
When you press a button, "OFF"
flashes on the LCD.

– Auto mode is not available if the-

re is no time schedule via bus.

Colder / Warmer


Fan mode button
– Automatic fan (

)

– Manual fan (

)



* Needs to be configured by your HVAC installer
** Needs to be enabled via parameter P02

Change room temperature

+ / –

Press + or to increase or decrease the current room temperature setpoint for
Comfort mode. The thermostat changes to Comfort .
The setting range is 5...40 °C, unless limited by parameters P09 and P10.

Adjust fan speed / fan mode



Press the button until you reach the desired fan mode.

In Auto mode, the thermostat automatically selects the fan speed based on set-
point and actual room temperature. The fan is switched off (factory setting) after
the room temperature reaches the setpoint .

In manual mode, the fan always runs at the speed that you select:
Low fan speed
Medium fan speed
High fan speed

Single-speed fan: You can change the mode between

and

.

Change thermostat operating







Press operating mode button to change the operating mode display.
In protection mode, the plant stops operating. However, if the room temperature
drops below 8 °C, heating is switched on to protect the room against frost.
Your HVAC installer can change the frost protection limit and set a heat pro-
tection limit as needed:
Changes made by installer:

Frost protection: ........... ˚C

Heat

protection:

...........

˚C

In Comfort mode, the thermostat maintains the room temperature on the
setpoint which can be readjusted using the + and – buttons.

In Economy mode, the room temperature is maintained at a lower or higher
setpoint, thus saving energy and money. Adjust parameters P11 and P12 to
change the preselected setpoints.
The thermostat can be set to Economy mode either by pressing the operating
mode button if enabled (P02 = 2), or via an external signal (switch or KNX bus
command) such as window contact, keycard or presence detector.

In Auto timer mode, the thermostat automatically switches between Comfort
and Economy mode according to the time schedule via KNX bus.

Change from heating to cooling mode

/

Changeover between cooling and heating is either automatic using a heating /
cooling changeover sensor or a remote changeover switch or via instruction from
the central management station via KNX bus, or manual by pressing operating
mode button . No changeover is possible if the thermostat is configured for
cooling only or heating only, (see parameter P01).

Display for automatic changeover or heating only / cooling only:

Heating valve is open
Cooling valve is open

Display for manual changeover:


Thermostat is in heating mode
Thermostat is in cooling mode