1 overview of oem settings – Siemens Albatros Zone Controler CE1U2353en01a User Manual
Page 4
4/26
Siemens Schweiz AG
User Manual OEM
CE1U2353en01a
HVAC Products
Overview of OEM settings 22.
November
2006
1 Overview of OEM settings
The table below shows all available settings up to the heating engineer level. However,
certain operating lines may be hidden, depending on the type of unit.
E = enduser I = commissioning F = heating engineer O = OEM
BZ = operating line
Operating line
User level
Function
Default value
Minimum
Max
Unit
Time of day and date
1
E Hours/minutes -
00:00
23:59
hh:mm
2
E Day/month -
01.01
31.12
dd.mm
3
E Year -
2004
2099
yyyy
5
F Start of summertime
25.03
01.01
31.12
dd.mm
6
F End of summertime
25.10
01.01
31.12
dd.mm
Operator section
20
E Language
German ¦ …
German
-
22
F Info
Temporarily ¦ Permanently
Temporarily
-
26
F Operation lock
Off ¦ On
Off
-
27
F Programming lock
Off ¦ On
Off
-
30 O
Data:read
No ¦ Yes
No
31 O
Data:write
No ¦ Yes
No
40
I
Used as
Room unit 1 ¦ Room unit 2 ¦ Operator unit ¦Service unit
Room unit 1
-
42
I
assignment room unit 1
Heating circuit 1 ¦ Heating circuits 1 and 2
Heating circuit 1
-
44
I
Operation HC2
Commonly with HC1 ¦ Independently
Commonly with HC1
-
46
I
Operation HCP
Commonly with HC1 ¦ Independently
Commonly with HC1
-
48
I
Action occupancy button
None ¦ Heating circuit 1 ¦ Heating circuit 2 ¦ Commonly
Heating circuit 1
-
54
F Readjustment room sensor
0.0
-3
3
°C
70
F Software version
-
0
99.9
-
Wireless
120
I
Binding
No ¦ Yes
No
121
I
Test mode
Off ¦ On
Off
130
I
Room unit 1
Missing ¦ Ready ¦ No reception ¦ Change batt
-
-
131
I
Room unit 2
Missing ¦ Ready ¦ No reception ¦ Change batt
-
-
132
I
Outside sensor
Missing ¦ Ready ¦ No reception ¦ Change batt
-
-
133
I
Repeater
Missing ¦ Ready ¦ No reception
-
-
Legend