3.13.4.3 Temporary interlock prohibition setting
(1) Click [Temporary prohibition].
(2) Temporary interlock prohibition setting screen
will appear.
* The pressed (sunken) button shows
the current status.
(3) Click the checkbox of the channel to be changed, and select [Disable] or [Enable].
(4) Click [Send settings].
(5) ”Settings will be sent. OK?”
will appear, click [Yes].
The setting will be applied to the unit.
(6) ”Settings have been sent.”will appear, click [OK].
(7) Click [Close] to return to the DIDO controller (66DC) Interlock control setting screen.
NOTE:
The “disable temporary interlock control (prohibition)” will be active for 15 minutes after the setting
has been sent, and will be inactive after 15 minutes have passed.
When the setting is sent again within 15 minutes before the “disable temporary interlock control ”
becomes inactive, the “disable temporary interlock control ” will be active again for another 15
minutes.
When the “enable temporary interlock control ” setting is sent during the “disable temporary interlock
control ” within 15 minutes, the “disable temporary interlock control ” will be inactive.