beautypg.com

GarrettCom 6K25 User Manual

Page 64

background image

Magnum 6K25 Managed Fiber Switch Installation and User Guide (04/06)

57

www GarrettCom com

.

.

B4.0 INSTALLATION

This section describes the installation of the -48 VDC, 24VDC and 125VDC

power source leads to the -48 VDC, 24VDC and 125VDC power terminal block on the

Magnum 6K25s. (see figure at right).

In this picture, the -48VDC

terminal block on the Magnum 6K25 is

located on the rear of the unit and is

equipped with three (3) screw-down

lead posts. It is similar for 24VDC and

125VDC options on Magnum 6K25.

The leads are identified as negative (-),

positive (+), Figure B4.0: -48VDC Terminal Block on Magnum 6K25-48VDC

and chassis ground (GND).

The actual connection procedure is very straightforward. Simply connect the

leads to the Magnum unit, beginning with ground. Ensure that each lead is securely

tightened.


Note: The GND should be hooked up first. The 6K25 unit has a floating ground, so the
user may elect to Ground either + or = terminal to suit the customer’s use.

Before connecting hot lines to the Terminal Block of –48VDC, 24VDC or

125VDC, always use a digital voltmeter to measure the output voltage of the power
supply and determine the lead which is more “+ve potential”. The more “+ve” voltage
lead from 48V or –48V supply must be connected to the post labeled “+”.

An ON-OFF manual switch is optional for DC power. This can be used to cut

off power connections and as a RESET for the Magnum 6K25 Switch.

B4.1

UL Requirements for DC-powered units

1. Minimum 18AWG cable for connection to a Centralized DC power source.
2. Minimum 14AWG cable for connection to a earthing wiring.
3. Use only with Listed 10 A circuit breaker provided in building installation.
4. “Complies with FDA radiation performance standards, 21 CFR subchapter J.”

or equivalent.

5. Fastening torque of the lugs on the terminal block: 9 inch-pound max.
6. Centralized DC Power Source cable securement, use at least four cable ties to

secure the cable to the rac,k at least 4 inches apart, with the first one located
within 6 inches of the terminal block.

36-70VDC

_

+

GND

ON

OFF