TEST 5 - CHECk STEPPER MOTOR CONTROL

PROCEDURE:
1. Remove air cleaner cover to access stepper motor.

2. Physically grab the throttle and verify the stepper motor, linkage

and throttle do not bind in any way, if any binding is felt repair
or replace components as needed. Some resistance should be
felt as the stepper motor moves through it's travel.

3. Physically move the throttle to the closed position by pushing

the throttle down as looking from above.

a. Place the idle control switch to off.
b. Place the start switch to start and watch for

stepper motor movement it should move to the

wide open position during cranking. Once the

unit starts the stepper motor should move the

throttle to a position to maintain 60 Hertz.

STEPPER
MOTOR

THROTTLE

LINKAGE

Figure 6-2. – Stepper Motor, Linkage and Throttle

Seen From Above

FULL THROTTLE

CLOSED THROTTLE

Figure 6-3. – Throttle Positions

4. If no movement is seen in Step 3 remove the control panel

cover. Verify the six pin connector on the printed circuit board is
seated properly, remove the connector and then replace it and
test again. Verify the switches are correctly set. See Figure 4-1
on Page 16 for positioning.

5. If problem continues remove six pin connector from printed cir-

cuit board. Set Volt meter to measure ohms. Carefully measure
from the end of the six pin harness as follows:

RED

EMPTY

ORANGE

BROWN

YELLOW

BLACK

Figure 6-4. – Six Pin Connector Wire Colors

NOTE: Press down with the meter leads on the

connectors exposed terminals, do not probe into

the connector.

a. Connect one meter lead to Red, connect the

remaining test lead to Orange, approximately 10

ohms should be measured.

b. Connect one meter lead to Red, connect the

remaining test lead to Yellow, approximately 10

ohms should be measured.

c. Connect one meter lead to Red, connect the

remaining test lead to Brown, approximately 10

ohms should be measured.

d. Connect one meter lead to Red, connect the

remaining test lead to Black, approximately 10

ohms should be measured.

e. Connect one meter lead to Red, connect the

remaining test to the stepper motor case. No

resistance should be measured INFINITY or

Open”

See Figure 6-4.
6. Set a voltmeter to measure DC voltage.

7. Connect the positive meter test lead to Wire 15B at Terminal

Block 1 (TB1). Connect the negative meter test lead to ground.
See Figure 6-5. Place the Start-Run-Stop Switch (SW1) to
START. 12 VDC should be measured. If voltage was measured
proceed to Step 8. If voltage was not measured, proceed to
"RESULTS".

8. Set a voltmeter to measure resistance.

9. Disconnect the J2 connector from the printed circuit board.

Connect one meter test lead to Pin Location J2-1 (Wire 15B.
Connect the other meter test lead to Wire 15B at Terminal
Block 1 (TB1). See Figure 6-6. Continuity should be measured.

section 6
Diagnostic tests