beautypg.com

Guardian Technologies 5209 User Manual

Page 13

background image

section 3

DescRiption & coMponents

2

162

Figure 3-5. – Excitation Circuit Breaker

VOLTAGE REGULATOR:
A typical Voltage Regulator is shown in Figure 3-6

(12.5 & 15 kW Units) or Figure 3-7 (17.5 kW Units).

Unregulated AC output from the stator excitation

winding is delivered to the regulator’s DPE termi-

nals, via Wire 2, the Excitation Circuit Breaker and

Wire 162, and Wire 6. The Voltage Regulator recti-

fies that current and, based on stator AC power

winding sensing, regulates it. The rectified and

regulated excitation current is then delivered to the

rotor windings from the positive (+) and negative (-)

regulator terminals, via Wire 4 and Wire 0. Stator

AC power winding “sensing” is delivered to the reg-

ulator “SEN” terminals via Wires 11S and 44S.
The regulator provides “over-voltage” protection, but

does not protect against “under-voltage”. On occur-

rence of an “over-voltage” condition, the regulator will

“shut down” and complete loss of excitation current

to the rotor will occur. Without excitation current, the

generator AC output voltage will drop to approximately

one-half (or lower) of the unit’s rated voltage.

Figure 3-6. – Typical Voltage Regulator Found on 12.5

kW and 15 kW Units

Figure 3-7. – Typical Voltage Regulator Found on 17.5

Units

ADJUSTMENT PROCEDURE (12.5 AND 15 KW UNITS):
The Voltage Regulator is equipped with three light

emitting diodes (LED’s). These LED’s are normally

on during operation with no faults in the system The

RED regulator LED is on when the regulator is on

and functioning. The Yellow sensing LED is powered

by sensing input to the regulator from the stator AC

power windings. The GREEN excitation LED is pow-

ered by stator excitation winding output.
Four adjustment potentiometers are provided. They

are VOLTAGE ADJUST, GAIN, STABILITY, and

UNDERFREQUENCY ADJUST.
1. Connect an AC Voltage/Frequency meter across wires 11 & 44

at the 50A Main circuit breaker. Verify frequency is between
59-61Hz.

2. On the regulator, set the adjustment pots as follows.

a. Voltage Adjust – Pot-turn fully counterclockwise
b. Gain – turn to midpoint (12 O’clock)
c. Stability – turn to midpoint (12 O’clock)
d. Under Frequency – turn to midpoint (12 O’clock)

3. Start the generator. This adjustment will be done under a no-

load condition.

4. Turn the regulator’s Voltage Adjust pot clockwise to obtain a line

to line voltage of 238-242 VAC.

5. If the red regulator LED is flashing, slowly turn the stability pot

either direction until flashing stops.

ADJUSTMENT PROCEDURE (17.5 KW UNITS):
A single red lamp (LED) glows during normal opera-

tion. The lamp will become dim if excitation winding

AC output diminishes. It will go out on occurrence of

an open condition in the sensing AC output circuit.
An adjustment potentiometer permits the stator AC

power winding voltage to be adjusted. Perform this

adjustment with the generator running at no-load, and

Page 11

This manual is related to the following products: