beautypg.com

Generac Power Systems Recreational Vehicle Generator 5413 User Manual

Page 45

background image

Section 7

DIAGNOSTIC TESTS

POSITIVE (+)
TEST LEAD

Figure 7-11. – Rotor Assembly

TEST 11 – CHECk MAIN CIRCUIT BREAkER

DISCUSSION:
The main circuit breaker on the generator panel must

be closed or no output to the load will be available.

A defective breaker may not be able to pass current

even though it is in the “ON” position.

CB2

CB1

33

11

BLACk

SCHEMATIC

PICTORIAL

RED

Figure 7-12. – Main Breaker (Typical)

PROCEDURE:
Set the coach main breaker to it’s “OFF” position.

Check that the appropriate main breaker on the gen-

erator panel is set to its “ON” (closed) position. Set a

VOM to measure resistance and use it to check for

continuity across the breaker terminals.

RESULTS:
1. If breaker is “ON” and “Continuity” is measured,

go to Test 3.

2. If breaker is “OFF”, reset to the “ON” position and

check for AC output.

3. If breaker is “ON” and “Continuity” is not mea-

sured, replace the defective circuit breaker.

TEST 12 – CHECk LOAd VOLTAgE &

FREqUENCY

DISCUSSION:
If engine speed appears to drop off excessively when

electrical loads are applied to the generator, the load

voltage and frequency should be checked.

PROCEDURE:
Perform this test in the same manner as Test 1, but

apply a load to the generator equal to its rated capac-

ity. With load applied check voltage and frequency.
Frequency should not drop below about 60 Hertz with

the load applied.
Voltage should not drop below about 120 VAC with

load applied.

RESULTS:
1. If voltage and/or frequency drop excessively when

the load is applied, go to Test 13.

2. If load voltage and frequency are within limits, end

tests.

TEST 13 – CHECk LOAd WATTS &

AMPERAgE

DISCUSSION:
This test will determine if the generator’s rated watt-

age/amperage capacity has been exceeded.
Continuous electrical loading should not be greater

than the unit’s rated capacity.

PROCEDURE:
Add up the wattages or amperages of all loads pow-

ered by the generator at one time. If desired, a clamp-

on ammeter may be used to measure current flow.

See “Measuring Current” on Page 16.

RESULTS:
1. If the unit is overloaded, reduce the load.
2. If load is within limits, but frequency and voltage

still drop excessively, complete Test 2, “Check

Stepper Motor Control”. If stepper motor adjust-

ment does not correct the problem, go to Problem

8 (Flow Chart, Pages 32 and 33).

Page 43