Section 6

TROUBLESHOOTING FLOWCHARTS

The “Flow Charts” in this section may be used in

conjunction with the “Diagnostic Tests” of Section 7.

Numbered tests in the Flow Charts correspond to

identically numbered tests of Section 7.

Problems 1 through 4 apply to the AC generator only.
Beginning with Problem 5, the engine DC control sys-

tem is dealt with.

Page 25

If Problem Involves AC Output

VOLTAGE &

FREQUENCY BOTH

HIGH OR LOW

FREQUENCY GOOD –

VOLTAGE HIGH

OR

VOLTAGE LOW

FREQUENCY GOOD –

ZERO OR RESIDUAL

VOLTAGE

NO-LOAD VOLTAGE

& FREQUENCY

GOOD

TEST 1 – CHECK

NO-LOAD VOLTAGE

& FREQUENCY

GO TO PROBLEM 1

GO TO VOLTAGE

REGULATOR ADUST-

MENT, PAGE xx

GO TO PROBLEM 2

GO TO PROBLEM 4

INTROdUCTION

Problem 1 – Voltage & Frequency Are Both High or Low

FREQUENCY GOOD.

LOW OR RESIDUAL

AC VOLTAGE

NO-LOAD FREQUENCY &

VOLTAGE GOOD BUT THEY

DROOP TO MUCH WHEN

LOAD IS APPLIED

FREQUENCY IS GOOD BUT

NO-LOAD VOLTAGE IS

HIGH OR VOLTAGE IS LOW

TEST 2 – CHECK

STEPPER MOTOR

CONTROL

GO TO

PROBLEM 2

GO TO

PROBLEM 4

GO TO VOLTAGE

REGULATOR

ADJUSTMENT,

PAGE 9