Icemaker troubleshooting chart

Flashing water LED at any time indicates that water signal to board had been lost for more than one second.

Ten-second delay: There is a 10 second delay in reaction to loss of water (WTR) or bin (B-E) signals. If signals are not
lost for more than 10 seconds, no reaction will occur.

Indicators/possible

cause

1. No power to unit.
2. Open bin level control.
3. Water OK LED (WTR) not on.
4. 20M or 2ND LED is on indicating

that first or second torque error has
occurred.

5. Gear motor locked up (immediate

torque error indicated by LEDs when
board is reset).

6. Open coil on gearmotor start relay

causing an immediate torque error.

1. Condenser coil plugged causing open

overload or high pressure cut-out.

2. Defective starting capacitor.
3. Defective starting relay.
4. Open motor winding.
5. No power output from compressor

output terminal on control board.


1. Float reservoir running dry, sensing

probe signalling for system to shut
down.

1. Dirty condenser coil.
2. Restricted air flow to condenser coil.
3. Mineral coated evaporator.
4. Improper exhaust air provisions.
5. Faulty expansion valve.
6. Low refrigerant charge.
7.

Superheat

incorrect.

8.

Inefficient

compressor.

1. O ring seal broken.

Corrective action

1. Check that unit is plugged in, circuit

breakers are on.

2. Adjust or replace ice level control.
3. Check reservoir for water, restore water

to unit.

4. See #6 below.
5. Repair or replace gear motor.
6. Replace gearmotor start relay.


1. Clean condenser coil and replace

overload if necessary.

2. Replace start capacitor.
3. Replace relay.
4. Ohm out windings and replace

compressor if necessary.

5. Check terminal connection and replace

control board if necessary.

1. Check water supply to float and float

operation. PC board will have flashing
WTR LED.

1. Clean

condenser.

2. Remove obstruction.
3. Clean evaporator.
4. Provide proper exhaust air provisions per

Follett installation manual.

5. Replace expansion valve.
6. Check for leaks; repair, evacuate, and

weigh in correct charge.

7. Check that TEV sensing bulb is securely

clamped in place and not damaged;
check that insulated bulb cover is in
place.

8. Replace compressor.

1. Replace O ring.

Problem

1. Icemaker

will

not

run.

System

status:

compressor,
gearmotor,
and fan motor
inoperative.

2. Compressor will

not run.

System

status:

gearmotor and
fan motor run.

3. Unit cycles

intermittently.

System

status:

compressor,
gear motor, and
fan motor cycle.

4. Low ice

production.

Poor quality ice.

5. Water leaks

from bottom of
evaporator.