beautypg.com

FieldServer Data Aire (DAP) FS-8704-49 User Manual

Page 8

background image

FS-8700-49_Data_Aire_DAP

Page 8 of 48


FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.FieldServer.com

Tel: (408) 262-2299 Fax: (408) 262-2269 Toll_Free: 888-509-1970 email: [email protected]

4.2.

Client Side Connection Descriptions

Connections
Column Title

Function

Legal Values

Port

This is the FieldServer port
connected to the DART’s RS-
232 port.

P1-P8, R1-R2

1

(P1-P8) requires 232/485
converter.

Secondary_Port*

The return loop from the DAP
devices is connected to this
port. (Loop connected to Tx+
& Tx- terminals.

P1-P8, R1-R2

1

(R1-R2) requires 232/485
converter.

Baud*

Specify baud rate

2400/9600

2

(Vendor

Limitation)

Parity*

Specify parity

None

Data_Bits*

Specify data bits

8

Stop_Bits*

Specify stop bits

1

Protocol

Specify protocol used. Either
keyword may be used.

DAP, Daire

Handshaking*

Specify hardware
handshaking

None

Poll Delay*

Time between internal polls

0-32000s, 1s

Example

//

Client Side Connections


Connections
Port, Secondary Port, Protocol, Baud, Parity, Data_Bits, Stop_Bits, Poll_Delay
R1,

R2,

DAP,

2400, None,

8,

1,

0.100s


1

Not all ports shown are necessarily supported by the hardware. Consult the appropriate Instruction

manual for details of the ports available on specific hardware.

2

DAP V9.5 or later supports 9600

Use this port identifier in the client side node
configuration described in Section 4.3.