FieldServer Data Aire (DAP) FS-8704-49 User Manual
Page 27
FS-8700-49_Data_Aire_DAP
Page 27 of 48
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.FieldServer.com
Tel: (408) 262-2299 Fax: (408) 262-2269 Toll_Free: 888-509-1970 email: [email protected]
Appendix B.2. DA_Func Parameter - Permitted values.
The driver supports a limited subset of the Dart Poll & Response Functions. The selection
of the sub-set is based on the identification of useful & practical functions.
In addition to the ‘Everything’ keyword indicated in chapter 4 the following specific query
functions are implemented.
Func.
Description
Driver Parameter
Protocol Id.
‘1’
DART Config Query
DA_Func = dart-config
49
‘2’
Dart Psswd Query
DA_Func = dart-password
50
'3'
DAP Config Command
DA_Func = dap-config
51
'4'
DAP Log Query
DA_Func = dap-log
52
'5'
DAP Unit-Type Query
DA_Func = dap-unit
53
'6'
DAP Stat Query
DA_Func = dap-stat
54
'7'
DAP Xtra Query
DA_Func = dap-xtra
55
'8'
DAP Menu Query
DA_Func = dap-menu
56
'A'
Chiller Stat Query
DA_Func = chiller-stat
65
'B'
Chiller Xtra Query
DA_Func = chiller-xtra
66
'C'
Chiller Menu Query
DA_Func = chiller-menu
67
‘D
Dart Status
DA_Func = dart-status
68
'E'
DAP80 Menu Query
DA_Func = dap80-menu
69
'G'
DAP Analog Query
DA_Func = dap80-analog
71
'H'
DAP Channels Query
DA_Func = dap80_channles
72
Each of the above queries returns a complex set of data consisting of many sub-fields.
Contact Data-Aire for a complete listing of the data composite returned.
The following special / diagnostic functions are also implemented.
Driver Parameter
Protocol Id.
DA_Func = All-Listen
11
DA_Func = Ack
6
DA_Func = Dart-Transparant
2
DA_Func = Dart-Opaque
3
DA_Func = Test-Echo
16
DA_Func = Test-No-Echo
15
DA_Func = Unit-Talk
13
With the exception of the Unit-Talk transmission of this command, these are nodeless
commands to allow the units time to switch their mechanical command. When using any of
these special commands no other DA_* fields need be specified.
All-Listen instructs the all units in the network to switch their relays to the listen position.
Those units already in the listen position will do nothing. Those in the talk position will first
echo the all-listen command and then switch their relays to the listen position. A pause of
0.15 seconds is required after the relays.