FieldServer Data Aire (DAP) FS-8704-49 User Manual

Page 42

background image

FS-8700-49_Data_Aire_DAP

Page 42 of 48


FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.FieldServer.com

Tel: (408) 262-2299 Fax: (408) 262-2269 Toll_Free: 888-509-1970 email: [email protected]

Byte Bit

Relative

Offset

Location in

Data Array

(Absolute

Offset) Each

alarm stored as

a separate bit

Location in Data

Array (Absolute

Offset) Each set

of 8 alarms
stored as a

byte*

046, 048 and 049 Units

DAP 80 Units

0

4

4

77

43:00

High Pressure Failure
Compressor No. 4

Humidifier problem:
check water
pressure

0

5

5

78

43:01

High Pressure Warning
Compressor No. 1

Low voltage
warning: check unit

0

6

6

79

43:02

High Pressure Warning
Compressor No. 2

Firestat alarm: unit
shutdown

0

7

7

80

43:03

High Pressure Warning
Compressor No. 3

Compressor short
cycle warning

1

0

8

81

46:00

High Pressure Warning
Compressor No. 4

Power problem or
unit restart

1

1

9

82

46:01

Low Pressure Failure
Compressor No. 1

Humidity sensor
problem

1

2

10

83

46:02

Low Pressure Failure
Compressor No. 2

Temperature sensor
problem

1

3

11

84

46:03

Low Pressure Failure
Compressor No. 3

Scheduled
maintenance due

1

4

12

85

44:04

Low Pressure Failure
Compressor No. 4

High pressure C1:
Manual reset
required

1

5

13

86

44:05

No Air Flow, Check Belt
and motor

Low pressure C1:
Manual reset
required

1

6

14

87

44:06

Change Filters, High
Pressure Drop

High pressure C2:
Manual reset
required

1

7

15

88

44:07

Local Alarm. See Tag
inside Door

Low pressure C2:
Manual reset
required

2

0

16

89

45:00

Manual Override, service
or emergency

Smoke detector: unit
shutdown

2

1

17

90

45:01

Humidifier Failure, Check
water pressure

No water flow: check
pump

2

2

18

91

45:02

No water flow. Check
glycol pump.

Discharge
temperature sensor
problem

2

3

19

92

45:03

Smoke detected, located
inside unit

High temperature
warning

2

4

20

93

45:04

Fire Stat Tripped, Location
inside unit

Low temperature
warning

2

5

21

94

45:05

Standby pump on, check
glycol pump

High humidity
warning

2

6

22

95

45:06

Low voltage warning,
check unit

Low humidity
warning

2

7

23

96

45:07

Water detected in under
floor area

Fan motor overload:
check motor
amperage