FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.FieldServer.com

Tel: (408) 262-2299 Fax: (408) 262-2269 Toll_Free: 888-509-1970 email: [email protected]

Byte Bit

Relative

Offset

Location in

Data Array

(Absolute

Offset) Each

alarm stored as

a separate bit

Location in Data

Array (Absolute

Offset) Each set

of 8 alarms
stored as a

byte*

046, 048 and 049 Units

DAP 80 Units

5

5

45

118

48:05

Custom message on
optional alarm input #1

N/A

5

6

46

119

48:06

Custom message on
optional alarm input #2

N/A

5

7

47

120

48:07

Custom message on
optional alarm input #3

N/A

6

0

48

121

49:00

Discharge air temperature
limit (just a condition)

N/A

6

1

49

122

49:01

Reheat mode during
dehumidification (just a
condition)

N/A

6

2

50

123

49:02

N/A

N/A

6

3

51

124

49:03

N/A

N/A

6

4

52

125

49:04

N/A

N/A

6

5

53

126

49:05

N/A

N/A

6

6

54

127

49:06

N/A

N/A

6

7

55

128

49:07

N/A

N/A

Notes

*

43:00 Indicates array
element zero. Individual
alarm can be found by
masking and looking at
the zero'th bit of this
element.

Chiller Stat Query
Unlike the Dap-Stat errors, these are stored in the Data Array using only one method –
each error is stored at a separate location in the Data Array.

Location in Data Array

(Absolute Offset) Each alarm

stored as a separate bit

Alarm / Bit Descriptions

Byte Bit

Relative

Offset

536

Auxiliary cooling available

0

0

0

537

Auxiliary cooling locked out

0

1

1

538

Unit on backup module standby

0

2

2

539

Custom message on optional input #1

0

3

3

540

Custom message on optional input #2

0

4

4

541

Evaporator freeze stat module #1

0

5

5

542

Evaporator freeze stat module #2

0

6

6

543

Evaporator freeze stat module #3

0

7

7

544

High pressure problem module #1

1

0

8

545

High pressure problem module #2

1

1

9

546

High pressure problem module #3

1

2

10

547

High return temperature warning

1

3

11

548

High supply temperature warning

1

4

12

549

Local alarm #1: See tag inside door

1

5

13