FieldServer Data Aire (DAP) FS-8704-49 User Manual

Page 22

background image

FS-8700-49_Data_Aire_DAP

Page 22 of 48


FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.FieldServer.com

Tel: (408) 262-2299 Fax: (408) 262-2269 Toll_Free: 888-509-1970 email: [email protected]

FieldServer

Array

Location

FieldServer Data

Field

Point Description

Message

Type

D/A Control Panel

Type

916

d_calib

Discharge Air sensor
calibration offset

DAP80 Menu

DAP80

917

esaver_supp_comp

Energy saver supplement
mode setting

DAP80 Menu

DAP80

918

fire_lim

Firestat temperature limit
setting

DAP80 Menu

DAP80

919

heater_config

Heating configuration

DAP80 Menu

DAP80

920

hi_h_lim

High humidity alarm limit
setting

DAP80 Menu

DAP80

921

hi_t_lim

High temperature alarm
limit setting

DAP80 Menu

DAP80

922

humid_config

Humidifier configuration

DAP80 Menu

DAP80

923

h_calib

Humidity calibration offset

DAP80 Menu

DAP80

924

h_dband

humidity deadband setting

DAP80 Menu

DAP80

925

lead_lag

Compressor lead/lag
setting

DAP80 Menu

DAP80

926

lo_d_lim

Low Discharge
temperature limit setting

DAP80 Menu

DAP80

927

lo_h_lim

Low humidity alarm limit
setting

DAP80 Menu

DAP80

928

lo_t_lim

Low temperature alarm
limit setting

DAP80 Menu

DAP80

929

main_int

Maintenance schedule
setting

DAP80 Menu

DAP80

930

network_id

set unit Network ID

DAP80 Menu

DAP80

931

nom_h_setpt

Humidity setpoint

DAP80 Menu

DAP80

932

password

password

DAP80 Menu

DAP80

933

ptc

Person to contact on
alarm message

DAP80 Menu

DAP80

934

relay_1_mask_0

selection for alarm contact

DAP80 Menu

DAP80

950

relay_1_mask_1

selection for alarm contact

DAP80 Menu

DAP80

966

relay_1_mask_2

selection for alarm contact

DAP80 Menu

DAP80

982

relay_2_mask_0

selection for alarm contact

DAP80 Menu

DAP80

998

relay_2_mask_1

selection for alarm contact

DAP80 Menu

DAP80

1014

relay_2_mask_2

selection for alarm contact

DAP80 Menu

DAP80

1030

relay_3_mask_0

selection for alarm contact

DAP80 Menu

DAP80

1046

relay_3_mask_1

selection for alarm contact

DAP80 Menu

DAP80

1062

relay_3_mask_2

selection for alarm contact

DAP80 Menu

DAP80

1078

reverse_valve

Chilled water direction
setting

DAP80 Menu

DAP80

1079

rst_mode

Restart mode setting

DAP80 Menu

DAP80

1080

sc_alarms

Compressor short cycle
setting

DAP80 Menu

DAP80

1081

s_delay

Start delay setting (in
seconds)

DAP80 Menu

DAP80

1082

t_calib

Temperature calibration
offset

DAP80 Menu

DAP80

1083

t_dband

Temperature deadband
setting

DAP80 Menu

DAP80

1084

t_setpt

Temperature setpoint

DAP80 Menu

DAP80