beautypg.com

Physical description of the fortigate-5050 chassis, Figure 2, Shows – Fortinet FortiGate 5050 User Manual

Page 7

background image

FortiGate-5050 chassis

Physical description of the FortiGate-5050 chassis

FortiGate-5050 Chassis Guide
01-30000-87211-20090106

7

http://docs.fortinet.com/

Feedback

Figure 2: FortiGate-5050 chassis back panel

The back panel includes the FortiGate-5050 chassis ground connector which must be
connected to Data Center ground. Use the power wire fixtures for securing and managing
DC power wires. The FortiGate-5050 chassis also includes an ESD socket on the back
panel.
For detailed information about connecting power to the FortiGate-5050 chassis, see

“Connecting the FortiGate-5050 chassis to data center DC power and data center ground”
on page 13

or

“Connecting the FortiGate-5050 chassis to AC power using the

FortiGate-5053 power converter tray” on page 15

.

The back panel also contains 5 RTM slots numbered to correspond to the front panel
slots. The RTM slots are available for FortiGate-5000 RTM modules such as the
FortiGate-RTM-XB2 module. When the FortiGate-5050 chassis is shipped, these slots are
covered by RTM slot filler panels.

Physical description of the FortiGate-5050 chassis

The FortiGate-5050 chassis is a 5U chassis that can be installed in a standard 19-inch
rack.

Table 1

describes the physical characteristics of the FortiGate-5050 chassis.

5

4

3

2

1

-48V to -58V

(-DC in)

(black)

Power

wire

Ground

Connector

(green)

-48V to -58V

(-DC in)

(black)

Positive

(RTN)

(red)

Positive

(RTN)

(red)

DC VOLTAGE RANGE

-48V TO -58V

RTN (-DC IN)

INPUT B

25

AMP

DC VOLTAGE RANGE

-48V TO -58V

RTN (-DC IN)

INPUT A

25

AMP

ESD

k t

RTN

GND

RTN

-48V

-48V

RTM

slot filler

panels

Table 1: FortiGate-5050 chassis

physical description

Dimensions

8.75 x 17 x 15.5 in. (13.3 x 43.2 x 39.4 cm)
(H x W x D)

Weight

26.75 lb. (12.1 kg)

Operating environment

Temperature: 32 to 104°F (0 to 45°C)
Relative humidity: 5 to 85% (Non-condensing)

Storage environment

Temperature: -13 to 158 °F (-25 to 70°C)
Relative humidity: 5 to 95% (Non-condensing)

Power consumption

Maximum: 1,135 W

Power input

2x redundant -48VDC to -58VDC