GUIDE SPECIFICATIONS (cont)

I. Controls and Safeties:

1. Unit Controls:

Unit shall be complete with self-contained low-
voltage control circuit protected by a fuse on the 24-v
transformer side.

2. Safeties:

a. Unit shall incorporate a solid-state compressor

protector which provides anti-cycle reset capabil-
ity at the space thermostat, should any of the
following standard safety devices trip and shut off
compressor.

1) Compressor overtemperature, overcurrent.
2) Loss-of-charge/low-pressure switch.
3) Freeze-protection thermostat, evaporator coil.
4) High-pressure switch.
The lockout protection shall be easily discon-
nected at the control board, if necessary.

b. Heating section shall be provided with the follow-

ing minimum protections:

1) High-temperature limit switches.
2) Induced draft motor speed sensor.
3) Flame rollout switch.
4) Flame proving controls

J. Operating Characteristics:

1. Unit shall be capable of starting and running at 125 F

ambient outdoor temperature, meeting maximum
load criteria of ARI Standard 210/240 or 360 at ±10%
voltage.

2. Compressor with standard controls shall be

capable of operation down to 25 F ambient outdoor
temperature.

K. Electrical Requirements:

All unit power wiring shall enter unit cabinet at a single
factory-predrilled location.

L. Motors:

1. Compressor motors shall be cooled by refrigerant

passing through motor windings and shall have line
break thermal and current overload protection.

2. Indoor blower (evaporator-fan) motor shall have per-

manently lubricated bearings and inherent
automatic-reset thermal overload protection.

3. Totally enclosed condenser-fan motor shall have

permanently lubricated bearings and inherent
automatic-reset thermal overload protection.

4. Induced-draft motor shall have permanently lubri-

cated, sealed bearings and inherent automatic reset
thermal overload protection.

M. Special Features:

Certain features are not applicable when the features
designated by * are specified. For assistance in amending
the specifications, contact your local sales office.

1. Roof Curbs:

a. Formed galvanized steel with wood nailer strip

and capable of supporting entire unit weight.

b. Allows for installing and securing ductwork to curb

prior to mounting unit on the curb.

*2. Integrated Economizers:

a. Integrated integral-modulating type capable of

simultaneous economizer and compressor
operation.

b. Includes all hardware and controls to provide

cooling with outdoor air.

c. Equipped with low-leakage dampers not to

exceed 3% leakage, at 1 in. wg pressure differen-
tial (Durablade economizer).

d. Capable of introducing up to 100% outdoor air in

both minimum and fully open positions.

e. Equipped with a gravity relief sliding plate damper

(Durablade economizer). Damper shall close
upon unit shutoff.

f. EconoMi$er shall be equipped with a barometric

relief damper with up to 100% of return air (036-
072) or 90% of return air (090-150) relief. The
Durablade economizer is equipped with 30% of
return-air relief (036-150).

g. Designed to close damper during loss-of-power

situations with emergency power supply (Dura-
blade economizer) or spring return built into
motor (EconoMi$er).

h. Dry bulb outdoor-air thermostat protection shall

be provided as standard.

i.

Durablade economizer is a guillotine-style
damper, and the EconoMi$er is a parallel blade
design.

3. 50% Manual Outdoor-Air Damper:

Manual damper package shall consist of damper,
birdscreen, and rainhood which can be preset
to admit up to 50% outdoor air for year-round
ventilation.

4. 25% Manual Outdoor-Air Damper:

Manual damper package shall consist of damper,
birdscreen, and rainhood which can be preset
to admit up to 25% outdoor air for year-round
ventilation.

5. 100% Two-Position Damper:

a. Two-position damper package shall include single

blade damper and motor. Admits up to 100% out-
door air.

b. Damper shall close upon indoor (evaporator) fan

shutoff.

c. Designed to close damper during loss of power

situations.

d. Equipped with 15% barometric relief damper.

6. 25% Two-Position Damper:

a. Two-position damper package shall include single

blade damper and motor. Admits up to 25% out-
door air.

b. Damper shall close upon indoor (evaporator) fan

shutoff.

*7. Solid-State Enthalpy Control:

a. For use with variable sliding economizer package

only.

b. Capable of sensing outdoor-air enthalpy content

(temperature and humidity) and controlling econ-
omizer cut-in point to have minimum heat content
air passing over the evaporator coil for most effi-
cient system operation.

*8. Differential Enthalpy Sensor:

a. For use with economizer only.

b. Capable of comparing enthalpy content (tempera-

ture and humidity) of outdoor and indoor air and
controlling economizer cut-in point at the most
economical level.

9. Outdoor-Air Enthalpy Sensor:

The outdoor-air enthalpy sensor shall be used with
the EconoMi$er device to provide single enthalpy
control. When used in conjunction with a return-air
enthalpy sensor, the EconoMi$er device will provide
differential enthalpy control. The sensor allows the
EconoMi$er controller to determine if outside air is
suitable for free cooling.

10. Return-Air Enthalpy Sensor:

The return-air enthalpy sensor shall be used with the
EconoMi$er device. When used in conjunction with
an outdoor-air enthalpy sensor, the EconoMi$er
device will provide differential enthalpy control.