PERFORMANCE DATA (cont)

COOLING CAPACITIES (cont)

Standard Ratings

LEGEND

NOTES:

1. Direct interpolation is permissible. Do not extrapolate.
2. The following formulas may be used:

Where h

ewb

= Enthalpy of air entering indoor coil.

3. The SHC is based on 80 F edb temperature of air entering evap-

orator coil.
Below 80 F db, subtract (corr factor x cfm) from SHC.
Above 80 F db, add (corr factor x cfm) to SHC.
Correction Factor = 1.10 x (1 – BF) x (db – 80).

581B060 (5 TONS)

Temp (F)

Air Ent

Condenser

(Edb)

Temp (F) Air Entering Evaporator — Cfm/BF

1500/0.08

1750/0.09

2000/0.11

2500/0.13

Temp (F) Air Entering Evaporator — Ewb (F)

72

67

62

72

67

62

72

67

62

72

67

62

75

TC

70.8

65.4

58.5

72.5

67.3

61.1

73.0

68.4

62.8

74.8

70.3

64.8

SHC

34.1

42.7

49.9

35.7

45.5

54.2

36.8

48.0

57.8

39.6

53.0

63.4

kW

3.53

3.49

3.44

3.55

3.50

3.46

3.55

3.51

3.47

3.57

3.54

3.48

85

TC

68.9

63.2

55.3

70.5

65.1

57.9

72.2

66.4

60.2

73.2

68.1

62.9

SHC

33.5

41.8

48.4

35.0

44.8

52.8

37.0

47.6

56.8

39.3

52.5

62.4

kW

3.98

3.94

3.87

4.00

3.96

3.90

4.03

3.97

3.92

4.04

3.99

3.94

95

TC

66.8

60.6

52.4

68.3

62.5

54.3

69.3

63.8

56.6

71.2

65.6

60.6

SHC

32.8

40.7

47.0

34.5

43.8

51.1

36.0

46.7

55.0

39.1

51.8

60.5

kW

4.48

4.43

4.35

4.50

4.45

4.37

4.51

4.46

4.40

4.55

4.48

4.44

105

TC

64.3

57.7

49.9

65.9

59.8

51.7

66.9

61.1

54.1

68.4

62.8

58.4

SHC

32.0

39.6

45.8

33.7

42.8

49.7

35.3

45.7

53.5

38.4

51.0

58.4

kW

5.03

4.96

4.87

5.05

4.99

4.90

5.06

5.00

4.93

5.08

5.02

4.98

115

TC

61.5

54.8

47.3

62.8

56.7

49.1

64.0

58.2

51.6

65.4

59.9

56.1

SHC

31.0

38.4

44.5

32.5

41.6

48.2

34.4

44.6

51.6

37.4

50.0

56.1

kW

5.61

5.55

5.46

5.62

5.58

5.49

5.65

5.60

5.52

5.67

5.61

5.57

125

TC

58.7

51.6

44.5

59.9

53.4

46.2

60.8

54.9

49.0

62.2

56.8

53.5

SHC

30.0

37.2

43.1

31.7

40.4

46.2

33.3

43.4

48.9

36.4

48.9

53.4

kW

6.27

6.19

6.09

6.28

6.21

6.13

6.29

6.24

6.17

6.31

6.27

6.22

581B072 (6 TONS)

Temp (F)

Air Ent

Condenser

(Edb)

Temp (F) Air Entering Evaporator — Cfm/BF

1800/0.05

2100/0.06

2400/0.06

3000/0.08

Temp (F) Air Entering Evaporator — Ewb (F)

72

67

62

72

67

62

72

67

62

72

67

62

75

TC

86.7

80.7

74.4

88.8

82.7

76.6

90.5

84.4

78.2

92.6

86.3

81.0

SHC

43.0

53.7

63.8

45.0

57.4

68.9

47.2

61.2

73.6

51.2

67.4

80.7

kW

4.58

4.46

4.33

4.63

4.50

4.38

4.67

4.55

4.41

4.72

4.58

4.47

85

TC

84.1

78.2

72.0

86.4

80.3

74.1

88.2

81.7

75.7

90.2

84.0

78.8

SHC

42.0

52.6

62.7

44.5

56.6

68.0

46.8

60.2

72.5

50.6

67.4

78.7

kW

5.10

4.97

4.85

5.16

5.03

4.90

5.21

5.06

4.93

5.26

5.12

4.99

95

TC

81.3

75.3

69.2

83.4

77.3

71.3

85.1

78.9

72.9

87.2

80.6

76.2

SHC

41.0

51.4

61.4

43.4

55.3

66.6

45.8

59.2

71.2

50.2

65.8

76.2

kW

5.65

5.52

5.39

5.71

5.57

5.44

5.77

5.62

5.48

5.83

5.66

5.55

105

TC

77.9

72.0

66.1

80.0

73.8

68.0

81.6

75.3

69.6

83.4

77.1

73.2

SHC

39.7

50.2

60.0

42.2

54.0

65.2

44.6

57.8

69.3

49.0

64.5

73.2

kW

6.22

6.08

5.94

6.29

6.13

6.00

6.34

6.17

6.04

6.40

6.22

6.12

115

TC

74.7

68.4

61.8

75.9

70.0

64.1

77.6

71.3

66.5

78.7

73.0

70.1

SHC

38.7

48.8

58.1

40.8

52.6

63.2

43.3

56.4

66.4

46.9

63.2

70.0

kW

6.84

6.68

6.49

6.87

6.71

6.56

6.93

6.75

6.63

6.96

6.80

6.72

125

TC

70.3

63.6

57.2

71.8

65.5

59.1

72.9

66.8

61.9

74.0

68.6

66.4

SHC

37.2

47.0

55.8

39.5

51.0

59.1

41.7

55.0

61.9

45.4

61.8

66.3

kW

7.43

7.25

7.03

7.48

7.30

7.13

7.51

7.35

7.22

7.54

7.41

7.33

BF

Bypass Factor

Edb — Entering Dry Bulb
Ewb — Entering Wet Bulb
kW

Compressor Motor Power Input

SHC — Sensible Heat Capacity (1000 Btuh) Gross
TC

Total Capacity (1000 Btuh) Gross

t

ldb

= t

edb

sensible heat capacity (Btuh)

1.10 x cfm

t

lwb

= wet-bulb temperature corresponding to enthalpy of air

leaving indoor coil (h

lwb

)

h

lwb

= h

ewb

total capacity (Btuh)

4.5 x cfm