Bryant COMMERCIAL SINGLE PACKAGE ROOFTOP GAS HEAT/ELECTRIC COOLING 581B User Manual

Page 18

background image

18

PERFORMANCE DATA

COOLING CAPACITIES

Standard Ratings

LEGEND

NOTES:

1. Direct interpolation is permissible. Do not extrapolate.
2. The following formulas may be used:

Where h

ewb

= Enthalpy of air entering indoor coil.

3. The SHC is based on 80 F edb temperature of air entering evap-

orator coil.
Below 80 F db, subtract (corr factor x cfm) from SHC.
Above 80 F db, add (corr factor x cfm) to SHC.
Correction Factor = 1.10 x (1 – BF) x (db – 80).

581B036 (3 TONS)

Temp (F)

Air Ent

Condenser

(Edb)

Temp (F) Air Entering Evaporator — Cfm/BF

900/0.14

1200/0.17

1500/0.20

Temp (F) Air Entering Evaporator — Ewb

72

67

62

72

67

62

72

67

62

75

TC

41.9

38.7

35.7

43.5

40.8

37.7

44.8

41.8

39.0

SHC

20.4

25.2

29.7

21.8

28.2

33.8

23.3

30.7

37.0

kW

2.19

2.16

2.12

2.21

2.18

2.15

2.23

2.19

2.16

85

TC

40.7

37.5

34.5

42.1

39.3

36.4

43.5

40.4

37.6

SHC

19.9

24.7

29.2

21.5

27.7

33.2

23.2

30.3

36.4

kW

2.46

2.42

2.39

2.47

2.44

2.41

2.50

2.45

2.42

95

TC

39.3

36.1

33.1

40.8

37.8

34.9

42.0

38.9

36.1

SHC

19.5

24.1

28.4

21.1

27.2

32.5

22.8

29.9

35.6

kW

2.75

2.71

2.66

2.77

2.73

2.69

2.79

2.74

2.71

105

TC

37.7

34.6

31.7

39.3

36.2

33.4

40.1

37.2

34.7

SHC

18.8

23.5

27.8

20.7

26.6

31.8

22.1

29.3

34.7

kW

3.06

3.02

2.98

3.09

3.04

3.01

3.10

3.06

3.03

115

TC

36.0

33.0

29.7

37.4

34.5

31.5

38.1

35.5

33.2

SHC

18.3

22.9

26.7

19.9

26.1

30.9

21.3

28.7

33.2

kW

3.41

3.36

3.31

3.43

3.39

3.34

3.44

3.41

3.37

125

TC

34.2

31.3

27.8

35.6

32.7

29.4

36.3

33.6

31.9

SHC

17.6

22.2

25.8

19.4

25.4

29.4

20.8

28.0

31.8

kW

3.78

3.73

3.66

3.80

3.76

3.71

3.81

3.78

3.75

581B048 (4 TONS)

Temp (F)

Air Ent

Condenser

(Edb)

Temp (F) Air Entering Evaporator — Cfm/BF

1200/0.17

1450/0.19

1600/0.21

2000/0.24

Temp (F) Air Entering Evaporator — Ewb (F)

72

67

62

72

67

62

72

67

62

72

67

62

75

TC

54.0

50.7

44.2

55.9

52.2

47.7

56.4

52.8

49.1

58.1

54.5

50.6

SHC

26.1

32.7

37.5

27.6

35.1

41.8

28.2

36.2

43.8

30.2

39.5

47.5

kW

2.81

2.80

2.76

2.83

2.81

2.78

2.83

2.80

2.79

2.84

2.82

2.79

85

TC

52.2

48.9

41.9

54.1

50.4

45.9

54.5

51.0

47.2

55.3

52.3

48.7

SHC

25.4

32.0

36.4

26.9

34.5

40.8

27.5

35.7

42.8

28.6

38.5

46.6

kW

3.20

3.19

3.15

3.22

3.20

3.17

3.22

3.20

3.18

3.22

3.20

3.18

95

TC

50.7

46.9

39.5

51.9

48.4

43.5

52.5

48.9

45.2

53.9

50.1

46.7

SHC

24.9

31.1

35.0

26.1

33.6

39.6

26.8

34.7

41.8

28.8

37.5

45.6

kW

3.64

3.61

3.57

3.65

3.62

3.60

3.65

3.62

3.60

3.67

3.63

3.61

105

TC

48.8

44.5

36.7

49.8

46.2

40.7

50.2

46.7

42.1

51.5

48.2

44.7

SHC

24.3

30.2

33.6

25.3

32.8

38.2

26.0

33.9

40.3

27.9

37.4

44.4

kW

4.12

4.09

4.03

4.12

4.09

4.06

4.12

4.09

4.07

4.14

4.11

4.08

115

TC

46.5

41.1

34.3

47.7

43.3

37.0

48.0

44.4

38.5

48.9

45.7

42.0

SHC

23.4

28.9

32.4

24.9

31.8

36.3

25.4

33.4

38.3

27.1

36.9

42.0

kW

4.64

4.59

4.53

4.65

4.62

4.55

4.64

4.63

4.56

4.65

4.63

4.60

125

TC

43.8

37.5

32.4

45.1

39.0

33.8

45.3

40.1

35.4

46.3

42.6

38.8

SHC

22.5

27.4

31.5

24.1

30.2

33.7

24.7

31.9

35.4

26.5

35.9

38.8

kW

5.19

5.13

5.05

5.20

5.15

5.09

5.19

5.17

5.11

5.20

5.19

5.15

BF

Bypass Factor

Edb — Entering Dry Bulb
Ewb — Entering Wet Bulb
kW

Compressor Motor Power Input

SHC — Sensible Heat Capacity (1000 Btuh) Gross
TC

Total Capacity (1000 Btuh) Gross

t

ldb

= t

edb

sensible heat capacity (Btuh)

1.10 x cfm

t

lwb

= wet-bulb temperature corresponding to enthalpy of air

leaving indoor coil (h

lwb

)

h

lwb

= h

ewb

total capacity (Btuh)

4.5 x cfm