beautypg.com

Bryant COMMERCIAL SINGLE PACKAGE ROOFTOP GAS HEAT/ELECTRIC COOLING 581B User Manual

Page 25

background image

25

PERFORMANCE DATA (cont)

COOLING CAPACITIES, UNITS WITH PERFECT HUMIDITY™ OPTION (cont)

LEGEND

NOTES:

1. Direct interpolation is permissible. Do not extrapolate.
2. The following formulas may be used:

Where: h

ewb

= Enthalpy of air entering evaporator coil.

3. The SHC is based on 80 F edb temperature of air entering evapo-

rator coil.
Below 80 F edb, subtract (corr factor x cfm) from SHC.
Above 80 F edb, add (corr factor x cfm) to SHC.
Correction Factor = 1.10 x (1 – BF) x (edb – 80).

581B120 (10 TONS)

Temp (F)

Air Ent

Condenser

(Edb)

Temp (F) Air Entering Evaporator — Cfm/BF

3000/0.03

3200/0.03

4000/0.04

5000/0.04

Temp (F) Air Entering Evaporator — Ewb

72

67

62

72

67

62

72

67

62

72

67

62

75

TC

134.3

122.5

111.4

135.8

124.3

113.0

138.4

129.5

123.5

143.3

136.5

130.2

SHC

60.0

76.1

93.7

61.3

79.1

97.4

68.0

89.5

109.4

75.2

100.9

123.3

kW

7.03

6.84

6.72

7.01

6.89

6.77

7.10

6.92

6.77

7.15

7.03

6.88

85

TC

127.6

115.4

104.6

128.9

118.1

107.0

132.5

121.5

116.6

137.2

128.0

122.9

SHC

51.5

68.8

87.2

53.9

72.0

91.2

61.0

82.7

102.4

68.6

93.6

115.9

kW

7.96

7.86

7.59

7.94

7.78

7.51

8.02

7.84

7.69

8.02

7.94

7.79

95

TC

120.9

108.3

97.8

121.9

111.8

101.0

126.5

113.4

109.7

131.1

119.4

115.5

SHC

43.0

61.5

80.6

46.5

64.8

84.9

53.9

75.9

95.4

62.0

86.2

108.4

kW

8.88

8.87

8.46

8.86

8.66

8.26

8.94

8.76

8.60

8.89

8.85

8.69

105

TC

112.0

99.9

90.4

113.1

103.2

93.4

117.2

105.0

100.7

122.1

110.5

105.9

SHC

36.1

54.1

73.8

38.8

57.8

78.9

45.6

68.2

86.8

53.0 78.3

99.7

kW

10.0

10.0

9.6

10.0

9.8

9.5

10.1

9.9

9.8

10.1

10.0

9.9

115

TC

103.0

91.5

83.1

104.3

94.6

85.9

107.8

96.7

91.7

113.0

101.6

96.4

SHC

29.2

46.7

66.9

31.2

50.7

72.9

37.3

60.6

78.3

44.0

70.3

90.9

kW

11.2

11.1

10.8

11.2

11.0

10.7

11.3

11.1

11.0

11.3

11.2

11.1

125

TC

94.1

83.1

75.7

95.5

86.0

78.3

98.5

88.3

82.7

104.0

92.7

86.8

SHC

22.3

39.3

60.1

23.5

43.7

66.8

29.0

52.9

69.7

35.0

62.4

82.2

kW

12.35

12.15

11.94

12.38

12.13

11.92

12.48

12.27

12.25

12.53

12.30

12.28

581B150 (12

1

/

2

TONS)

Temp (F)

Air Ent

Condenser

(Edb)

Temp (F) Air Entering Evaporator — Cfm/BF

3750/0.08

4300/0.09

5000/0.11

6250/0.13

Temp (F) Air Entering Evaporator — Ewb

72

67

62

72

67

62

72

67

62

72

67

62

75

TC

156.3

144.2

132.3

160.0

148.4

136.2

162.8

150.6

138.2

169.0

157.5

145.6

SHC

66.6

87.6

112.1

72.5

94.8

121.3

76.9

99.6

127.5

87.0

115.5

142.7

kW

9.28

8.98

8.59

9.35

9.08

8.80

9.40

9.18

8.9

9.43 9.18

8.93

85

TC

147.6

136.2

123.7

150.7

140.1

127.2

154.1

140.8

127.9

161.1

148.0

135.4

SHC

58.7

80.0

103.8

63.5

86.5

112.2

68.7

91.0

118.1

77.7

107.8

133.2

kW

10.29

9.93

9.58

10.36

10.08

9.77

10.40

10.34

10.03

10.45

10.18

9.88

95

TC

138.9

128.2

115.1

141.4

131.8

118.3

145.3

131.0

117.6

153.1

138.4

125.1

SHC

50.8

72.3

95.5

54.4

78.1

103.2

60.5

82.3

108.7

68.5

100.0

123.7

kW

11.29

10.87

10.57

11.37

11.08

10.74

11.40

11.50

11.1

11.46

11.17

10.83

105

TC

129.1

117.8

105.8

131.7

121.0

108.7

134.8

119.9

107.7

140.9

126.9

115.9

SHC

42.1

63.5

86.5

45.4

69.0

93.9

51.2

74.2

101.3

57.7

90.2

113.6

kW

12.59

12.14

11.82

12.67

12.34

11.96

12.70

12.67

12.28

12.79

12.46

12.08

115

TC

119.2

107.3

96.4

122.1

110.2

99.0

124.2

108.8

97.8

128.7

115.3

106.7

SHC

33.5

54.8

77.5

36.4

59.8

84.7

41.9

66.1

93.8

46.8

80.5

103.5

kW

13.90

13.40

13.08

13.98

13.59

13.18

14.00

13.83

13.41

14.11

13.75

13.33

125

TC

109.4

96.9

87.1

112.4

99.4

89.3

113.7

97.7

87.8

116.5

103.8

97.5

SHC

24.8

46.0

68.5

27.4

50.7

75.5

32.6

58.0

86.4

36.0

70.7

93.5

kW

15.20

14.67

14.33

15.28

14.85

14.40

15.30

15.00

14.54

15.44

15.04

14.58

BF

Bypass Factor

Edb

Entering Dry Bulb

Ewb — Entering Wet Bulb
kW

Compressor Motor Power Input

SHC — Sensible Heat Capacity (1000 Btuh) Gross
TC

Total Capacity (1000 Btuh) Gross

t

ldb

= t

edb

sensible capacity (Btuh)

1.10 x cfm

t

lwb

= Wet-bulb temperature corresponding to enthalpy of air

leaving evaporator coil (h

lwb

)

h

lwb

= h

ewb

total capacity (Btuh)

4.5 x cfm