beautypg.com

Bryant COMMERCIAL SINGLE PACKAGE ROOFTOP GAS HEAT/ELECTRIC COOLING 581B User Manual

Page 23

background image

23

PERFORMANCE DATA (cont)

COOLING CAPACITIES, UNITS WITH PERFECT HUMIDITY™ OPTION (cont)

LEGEND

NOTES:

1. Direct interpolation is permissible. Do not extrapolate.
2. The following formulas may be used:

Where: h

ewb

= Enthalpy of air entering evaporator coil.

3. The SHC is based on 80 F edb temperature of air entering evapo-

rator coil.
Below 80 F edb, subtract (corr factor x cfm) from SHC.
Above 80 F edb, add (corr factor x cfm) to SHC.
Correction Factor = 1.10 x (1 – BF) x (edb – 80).

581B060 (5 TONS)

Temp (F)

Air Ent

Condenser

(Edb)

Temp (F) Air Entering Evaporator — Cfm/BF

1500/0.08

1750/0.09

2000/0.11

2500/0.13

Temp (F) Air Entering Evaporator — Ewb

72

67

62

72

67

62

72

67

62

72

67

62

75

TC

69.9

62.7

56.2

74.7

67.3

61.0

78.5

71.2

64.8

81.7

75.5

69.3

SHC

29.0

36.9

43.9

31.7

40.5

51.2

34.5

44.2

55.4

37.8

52.0

62.8

kW

3.61

3.55

3.51

3.64

3.58

3.49

3.65

3.60

3.51

3.62

3.58

3.51

85

TC

65.9

59.1

51.7

70.6

63.2

56.3

75.5

66.8

60.7

78.1

70.8

65.1

SHC

25.3

34.0

41.9

27.5

37.6

48.0

30.7

41.6

52.0

33.8

47.4

58.0

kW

4.05

3.97

3.91

4.07

4.01

3.92

4.11

4.00

3.95

4.08

4.02

3.96

95

TC

61.9

55.2

47.7

66.5

58.8

51.3

70.4

61.9

55.7

74.2 65.9

60.6

SHC

21.6

31.1

40.0

23.5

34.5

44.6

26.0

38.6

47.9

30.0

42.8

52.6

kW

4.53

4.43

4.35

4.55

4.47

4.37

4.56

4.42

4.41

4.58

4.49

4.44

105

TC

57.7

51.1

44.9

61.8

54.5

47.7

65.1

57.2

50.8

68.4

60.3

56.1

SHC

18.1

27.8

35.7

20.0

31.2

40.1

22.1

34.3

43.5

26.1

38.9

48.5

kW

5.05

4.93

4.84

5.09

4.97

4.88

5.11

4.96

4.92

5.11

5.03

4.98

115

TC

53.4

47.2

42.0

56.6

50.0

44.2

59.6

52.5

46.2

62.6

54.9

51.6

SHC

14.7

24.6

31.5

16.5

27.8

35.7

18.2

30.0

39.0

22.1

34.9

44.3

kW

5.60

5.49

5.40

5.64

5.52

5.45

5.69

5.55

5.48

5.69

5.61

5.57

125

TC

48.7

42.0

36.9

51.3

45.0

39.0

54.1

46.8

40.9

56.9

49.2

45.9

SHC

10.9

19.6

28.0

12.5

22.2

31.5

13.5

24.0

34.0

16.5

28.0

38.8

kW

6.26

6.12

6.02

6.28

6.18

6.09

6.33

6.18

6.13

6.33

6.27

6.22

581B072 (6 TONS)

Temp (F)

Air Ent

Condenser

(Edb)

Temp (F) Air Entering Evaporator — Cfm/BF

1800/0.05

2100/0.06

2400/0.06

3000/0.08

Temp (F) Air Entering Evaporator — Ewb

72

67

62

72

67

62

72

67

62

72

67

62

75

TC

82.6

75.6

68.5

84.9

78.0

70.9

85.9

79.5

73.5

89.1

82.7

77.0

SHC

36.0

44.8

55.4

37.5

49.1

59.7

38.8

51.1

64.0

41.8

58.1

70.2

kW

4.60

4.52

4.36

4.67

4.57

4.46

4.70

4.57

4.45

4.77

4.61

4.51

85

TC

78.2

71.6

64.5

80.9

73.4

65.8

82.0

74.4

67.9

85.8

78.2

72.3

SHC

31.4

41.2

51.7

33.0

44.7

55.8

34.7

47.4

60.1

37.6

54.3

66.7

kW

5.16

5.03

4.89

5.22

5.11

4.96

5.26

5.09

4.97

5.32

5.17

5.04

95

TC

73.8

67.4

60.2

76.3

68.3

60.5

77.5

69.3

62.3

82.0

72.8

67.5

SHC

27.0

37.6

47.9

28.2

40.0

51.6

30.2

43.7

56.2

33.6

49.2

62.9

kW

5.75

5.60

5.44

5.80

5.66

5.48

5.84

5.68

5.53

5.90

5.73

5.60

105

TC

68.4

62.6

55.9

71.4

64.3

56.2

72.1

64.6

58.3

75.7

67.0

62.4

SHC

22.3

33.5

43.5

23.4

36.5

48.0

25.4

38.4

50.2

29.1

45.2

56.2

kW

6.37

6.22

6.06

6.45

6.27

6.10

6.46

6.29

6.16

6.53

6.36

6.24

115

TC

63.4

57.8

50.7

66.0

60.1

51.5

66.4

59.6

54.5

68.8

60.8

57.5

SHC

18.1

29.5

38.9

18.8

32.9

44.1

20.7

33.3

43.8

24.3

41.4

49.7

kW

7.04

6.89

6.68

7.10

6.91

6.74

7.12

6.95

6.83

7.16

7.01

6.92

125

TC

55.5

49.6

45.8

58.4

52.4

46.1

57.6

52.1

49.5

59.2

52.8

53.1

SHC

15.3

24.0

35.2

15.7

27.5

39.0

17.5

27.5

38.4

20.9

34.6

44.4

kW

7.80

7.61

7.38

7.83

7.67

7.49

7.89

7.72

7.58

7.92

7.78

7.70

BF

Bypass Factor

Edb

Entering Dry Bulb

Ewb — Entering Wet Bulb
kW

Compressor Motor Power Input

SHC — Sensible Heat Capacity (1000 Btuh) Gross
TC

Total Capacity (1000 Btuh) Gross

t

ldb

= t

edb

sensible capacity (Btuh)

1.10 x cfm

t

lwb

= Wet-bulb temperature corresponding to enthalpy of air

leaving evaporator coil (h

lwb

)

h

lwb

= h

ewb

total capacity (Btuh)

4.5 x cfm