beautypg.com

10 physical data (cont) – Bryant COMMERCIAL SINGLE PACKAGE ROOFTOP GAS HEAT/ELECTRIC COOLING 581B User Manual

Page 10

background image

10

PHYSICAL DATA (cont)

LEGEND

*Single phase/three phase.

†Indicates automatic reset.

**581B 072 unit size 036-072 (72,000 Btu heat input) have 2 burners.

581B 115 unit size 036-072 (115,000 Btu heat input) have 3 burners.
581B 150 unit size 048-072 (150,000 Btu heat input) have 3 burners.

††An LP kit is available as an accessory.

llCalifornia compliant three-phase models.

***Three-phase standard models have heating inputs as shown. Single-

phase standard models have one-stage heating with heating input values
as follows:

581BJV036-060072, 72,000 Btuh
581BJV036-060115, 115,000 Btuh
581BJV048-060150, 150,000 Btuh

†††California SCAQMD compliant Low NO

x

models have combustion prod-

ucts that are controlled to 40 nanograms per joule or less.

UNIT SIZE 581B

036

048

060

072

FURNACE SECTION

Rollout Switch Cutout Temp (F)†

195

195

195

195

Burner Orifice Diameter (in. ...drill size)**
Natural Gas — Std

071/072

.113...33

.113...33

.113...33

.113...33

114/115

.113...33

.113...33

.113...33

.113...33

149/150

.129...30

.129...30

.129...30

060N

.102...38

.102...38

.102...38

090N

.102...38

.102...38

.102...38

120N

.116...32

.116...32

Liquid Propane — Alt††

071/072

.089...43

.089...43

.089...43

.089...43

114/115

.089...43

.089...43

.089...43

.089...43

149/150

.102...38

.102...38

.102...38

060N

.082...45

.082...45

.082...45

090N

.082...45

.082...45

.082...45

120N

.094...42

.094...42

Thermostat Heat Anticipator Setting (amps)

(208/230/460/575 V)

.14

.14

.14

.14

Gas Input (Btuh)

First Stage/Second Stage

071II

—/ 72,000

—/ 72,000

—/ 72,000

114II

—/115,000

—/115,000

—/115,000

149II

—/150,000

—/150,000

072***

50,000/ 72,000

50,000/ 72,000

50,000/ 72,000

50,000/ 72,000

115***

82,000/115,000

82,000/115,000

82,000/115,000

82,000/115,000

150***

120,000/150,000

120,000/150,000

120,000/150,000

060N†††

—/ 60,000

—/ 60,000

—/ 60,000

090N†††

—/ 90,000

—/ 90,000

—/ 90,000

120N†††

—/120,000

—/120,000

Efficiency (Thermal) (%)

071

82

82

82

114

80

81

81

149

80

80

072

82

82

82

82

115

80

81

81

81

150

80

80

80

060N

81

81

81

090N

81

81

81

120N

82

82

Temperature Rise Range

071

15-45

15-45

15-45

114

55-85

35-65

35-65

149

50-80

50-80

072

15-45

15-45

15-45

15-45

115

55-85

35-65

35-65

35-65

150

50-80

50-80

50-80

060N

20-50

20-50

20-50

090N

30-60

30-60

30-60

120N

40-70

40-70

Manifold Pressure (in. wg)

Natural Gas — Std

3.5

3.5

3.5

3.5

Liquid Propane — Alt††

3.5

3.5

3.5

3.5

Maximum Static Pressure (in. wg)

1.0

1.0

1.0

1.0

Field Gas Connection Size (in.)

1

/

2

1

/

2

1

/

2

1

/

2

HIGH-PRESSURE SWITCH (psig)

Standard Compressor Internal Relief

450 ± 50

Cutout

428

Reset (Auto.)

320

LOSS-OF-CHARGE SWITCH/LOW-PRESSURE SWITCH

(Liquid Line) (psig)

Cutout

7 ± 3

Reset (Auto.)

22 ± 5

FREEZE PROTECTION THERMOSTAT

Opens (F)

30 ± 5

Closes (F)

45 ± 5

OUTDOOR-AIR INLET SCREENS

Cleanable

Quantity...Size (in.)

1...20 x 24 x 1

RETURN-AIR FILTERS

Throwaway

Quantity...Size (in.)

2...16 x 25 x 2

Bhp — Brake Horsepower