beautypg.com

Precision air conditioning, Smartcool, W 2 w2 – Airedale SmartCool 11-233kW User Manual

Page 97: Mechanical data – w2w2 continued

background image



Precision Air Conditioning


SmartCool

TM

– D

Precision Air Conditioning

97

Installation, Maintenance and Commissioning Manual :6877419 02/2013

Mechanical Data – W2W2 Continued

SC31D100-W2W2

SC31D120-W2W2

SC31D130-W2W2

2 x DR70

2 x DR95

2 x DR95

Capacity

(1)

Nom Cooling (Gross) – W2

kW

98.6

112.4

120.2

Total Heat of Rejection – W2

kW

126.6

144.6

154.7

Capacity Steps

6

4

6

Fan Gain

(5)

kW

1.46

2.51

3.22

Dimensions – W x D x H

Mm

3113 x 890 x 1980

3113 x 890 x 1980

3113 x 890 x 1980

Weight – Machine / Operating

Kg

1390 / 1400

1400 / 1410

1400 / 1420

Construction

Panels: Galvanised Sheet Steel, Epoxy Baked Powder Paint - Black Grey (RAL

7021)

Material/Colour

Frame:Anodised Aluminium Frame with Black Nylon Corners

Evaporator

Rifled Copper Tube/Turbulated Hydrophilic Coated Aluminium Fins

Cooling/Dehum Stages

6/1

4/1

6/1

Condenser

Stainless Steel Brazed Plate

Water Volume

l

16.7

16.7

16.7

Water Flow

l/s

3.09

3.53

3.78

Pressure Drop Condenser

kPa

27.88

35.79

40.63

Dry Cooler

Water Volume

l

55.9

55.9

55.9

Flowrate

l/s

3.09

3.53

3.78

Pressure drop

kPa

52

62

70.2

Fan Motor

Backwards Curved, Centrifugal direct drive

Motor Type

EC

EC

EC

Quantity x Motor Size

kW

3 x 3.1

3 x 3.1

3 x 3.1

Speed @25Pa / Maximum ESP

RPM

1116 / 1510

1347 / 1520

1480 /1510

Maximum ESP

Pa

478

232

77

Nominal Airflow

m³/s

6.1

7.3

7.9

Compressor – Scroll

Configuration – W2W2

Dual Circuit - Circuit 1 Tandem Compressors (Refrigeration)

Circuit 2 Tandem Compressors (Refrigeration)

Quantity – W2W2

2

2

2

Oil Charge Volume – W2W2

l

2 x 3 + 2 x 3.3

2 x 3.3

2 x 3.3

Oil Type

Polyolester

Refrigeration

Dual Circuit

Refrigerant control and type

Thermostatic Expansion Valve (Optional EEV)

Refrigerant type

R410A

Holding Charge

Inert Gas

Charge (Per Circuit)

kg

12

12

12

Connections

Water Inlet / Outlet –W2

mm

42

42

42

Condensate Drain Hose

mm

22

22

22

Filtration

Disposable to BS EN 779-G4

Quantity

4

4

4

OPTIONAL EXTRAS

Hot Gas Reheat -

(3)

Nom Heating (Gross)

kW

14.6

15.8

16.3

Electric Heating (Total)

kW

31.5

31.5

31.5

Humidifier

Capacity

kg/hr

15

15

15

Feed/Drain

3/4" BSPF Braided flexible hose / 19mm hose connection

Condensate Pump

Head

m

10.8

10.8

10.8

Flow

l/m

5

5

5

Drain

10mm Stainless steel Stub Connection

First upgrade Motor - EC Motor

Quantity x Motor Size

kW

N/A

N/A

N/A

Speed @ 25Pa / Maximum ESP

rpm

N/A

N/A

N/A

Maximum ESP

Pa

N/A

N/A

N/A

Fan Gain

kW

N/A

N/A

N/A

Second upgrade Motor - EC Motor

Quantity x Motor Size

kW

N/A

N/A

N/A

Speed @ 25Pa / Maximum ESP

rpm

N/A

N/A

N/A

Maximum ESP

Pa

N/A

N/A

N/A

Fan Gain

(5)

kW

N/A

N/A

N/A

Low Pressure Hot Water

(4)

Copper Tube/Aluminium Fin

Capacity Gross

kW

40.6

43.8

45.2

Water Flow (Nominal)

l/s

0.9

0.97

1.01

Pressure drop

kPa

35.9

37.4

38.8

LPHW Connection Sizes

(5)

mm

22

22

22

(1) Entering air 24°C/45% RH condensing water in / out: 35/40°C
(2) Machine weight Includes a refrigerant charge / Operating weight includes calculated water volume
(3) Based on air temperature of 15.5 °C

leaving the evaporator coil

(4) Based upon low pressure hot water 82 °Cinlet/71°C outlet. Air on 20°C.
(5) Fan gain based on 25 Pa ESP @ nominal air volume. Fan gain figure will change as airflow and ESP change.

W

2