Smartcool, Precision air conditioning, W 2 f0 – Airedale SmartCool 11-233kW User Manual

Page 142: Cable installation, Indoor controls only, Remote on/off, Run/standby network

background image


SmartCool

TM

- D

Precision Air Conditioning

142

Precision Air Conditioning

Installation, Maintenance and Commissioning Manual :6877419 02/2013


Non Sub Fused Three Phase SCAF Dry Cooler (DR95)

Fan Speed Control Fitted
to Outdoor Unit (No sub
fusing available)

INDOOR

UNIT

L1

¡

ç

Separate Mains Incoming

Supply

400V / 3PH + N / 50Hz

Separate Mains

Incoming Supply

400V / 3PH / 50Hz

è

¡

L1

OUTDOOR 1

L2

¡

з

и

¡

L2

L3

¡

з

и

¡

L3

CIRCUIT 1

N

¡

з

и

¡

PE

¡

з

и

¡

PE

833

¡

è

Fan Speed Control Signal to Outdoor Unit 1

и

¡

833

500

¡

и

и

¡

500

SCR

¡

и

и

¡

SCR

Indoor Controls Only

INDOOR

UNIT

560

¡

è

Volt Free Alarm N/O

Non-Critical Alarm

561

¡

ç

Volt Free Alarm Common

563

¡

è

Volt Free Alarm N/O

Critical Alarm

564

¡

ç

Volt Free Alarm Common

565

¡

è

Volt Free Alarm N/C

502

¡

è

Fire Shutdown input

583

¡

ç

Healthy in N/C Condition

Remote On/Off

INDOOR

UNIT

502

¡

è

Remote On/OFF

522

¡

ç

Run/Standby Network

INDOOR

UNIT

Rx-/Tx-

¡

çè

Use Awg20/22 twisted pair (with overall shield)

cable, Belden ref. 8762 (Airedale ref:

6110316), or equivalent, for

network

çè

¡

Rx-/Tx-

INDOOR

UNIT
N + 1

Rx+/Tx+

¡

зи

зи

¡

Rx+/Tx+

GND

¡

зи

зи

¡

GND


CABLE INSTALLATION

In line with IEE Wiring Regulations, the following should be observed:
·

Extra low voltage control cables (ELV) and mains power cable should be segregated by a
minimum distance of 50mm

·

If cables must cross, it is recommended that they cross at right angles

·

Airedale recommends that ELV cables are screened at one end to earthed enclosures


W

2

F0