Smartcool, Precision air conditioning – Airedale SmartCool 11-233kW User Manual
Page 178
SmartCool
TM
- D
Precision Air Conditioning
178
Precision Air Conditioning
Installation, Maintenance and Commissioning Manual :6877419 02/2013
Evaporator Fan removal
Stage 1 Inlet Ring
·
Remove door panel – 6 off
M6 Countersunk screws.
·
Unscrew 6 off M5 bolts that
retain inlet ring in position.
·
Lift inlet ring free of aperture.
Stage 2 Remove Door
Divider Rail
·
Remove door divider
assembly.
(Fixed top and bottom.)
Stage 3 Slide Fan Forward
·
Disconnect fan loom from
electrical control panel.
·
Remove 4 off M6 bolts that
hold the fan support.
·
Slide fan assembly towards
the front of the unit (along
fan support guide rails.
·
Carefully lift out the fan
assembly taking care not to
damage the fan loom.
Standard AC Fan
EC Fan
Upgraded EC Fan
Fan Weights
kg
28
23.5
27.5
Note: Weights not including base plate.
M
a
in
te
n
a
n
ce