beautypg.com

Smartcool, Precision air conditioning, X2 c0 – Airedale SmartCool 11-233kW User Manual

Page 88: Electrical data – x2c0 continued

background image


SmartCool

TM

- D

Precision Air Conditioning

88

Precision Air Conditioning

Installation, Maintenance and Commissioning Manual :6877419 02/2013


Electrical Data – X2C0 Continued

SC31D055-X2C0-0

SC31D065-X2C0-0

SC31D075-X2C0-0

Standard Condenser Match

1 x CR80

1 x CR105

1 x CR105

Unit Data Full Function- X2C0

Nominal Run Amps

A

81.6

85.7

85.7

Maximum Start Amps

A

175.3

198.7

212.4

Recommended Mains Fuse Size

A

100

100

100

Max Mains Incoming Cable Size

mm²

35

35

35

Mains Supply

V

400V / 3PH + N / 50Hz

Control circuit

VAC

24

24

24

Unit Data Cooling Only – X2C0

Nominal Run Amps

A

53.6

57.6

59.9

Maximum Start Amps

A

166.6

170.7

203.7

Recommended Mains Fuse Size

A

63

80

80

Evaporator Fan Motor - Per Fan

Motor Type

EC

EC

EC

Quantity x Motor Size

kW

3 x 3.1

3 x 3.1

3 x 3.1

Full Load Amps

A

4.8

4.8

4.8

Locked Rotor Amps

A

4.8

4.8

4.8

Compressor 1 , Circuit 1

Motor Size

kW

7.19

9.46

9.46

Nominal Run Amps

A

12.87

16.93

16.93

Locked Rotor Amps

A

92

130

130

Type of Start

Direct On Line

Compressor 2, Circuit 1

Motor Size

kW

9.46

9.46

10.86

Nominal Run Amps

A

16.9

16.9

19.2

Locked Rotor Amps

A

130

130

163

Type of Start

Direct On Line

Standard Condenser Match - AC Motor Per Fan

Quantity x Motor Size

kW

3 x 0.6

3 x 0.6

3 x 0.6

Full Load Amps

A

2.62

2.62

2.62

OPTIONAL EXTRAS

Electric Heating

Number of stage of Reheat

3

3

3

Number of Elements

9

9

9

Rating (Total)

kW

31.5

31.5

31.5

Current Per Phase

A

45.47

45.47

45.47

Humidifier

Capacity

kg/hr

8

8

8

Rating

kW

6

6

6

Full Load Amps

A

8.67

8.67

8.67

First upgrade Fan Motor - EC Motor - Per Fan

Quantity x Motor Size

kW

N/A

N/A

N/A

Full Load Amps

A

N/A

N/A

N/A

Locked Rotor Amps

A

N/A

N/A

N/A

Second upgrade Motor - EC Motor - Per Fan

Quantity x Motor Size

kW

N/A

N/A

N/A

Full Load Amps

A

N/A

N/A

N/A

Locked Rotor Amps

A

N/A

N/A

N/A

Standard Condenser Match - EC Motor-Per Fan

Quantity x Motor Size

kW

3 x 0.73

3 x 0.73

3 x 0.73

Full Load Amps

A

3.3

3.3

3.3

Condenser Match - SCAF Fan

Quantity x Motor Size

kW

3 x 1.4

3 x 1.4

3 x 1.4

Full Load Amps

A

6

6

6

(1) Values given for function units with standard selections for heating, humidification, supply air fans and matched condenser
at 7°C evaporating and 54.4°C condensing
(2) Stated motor power is based on maximum electrical power absorbed

(3) Values are per compressor

X2