Precision air conditioning, Smartcool, C 0 c0 – Airedale SmartCool 11-233kW User Manual
Page 157: Electrical data - c0c0 continued
Precision Air Conditioning
SmartCool
TM
– D
Precision Air Conditioning
157
Installation, Maintenance and Commissioning Manual :6877419 02/2013
Electrical Data - C0C0 Continued
SC31D55-C0C0-0
SC31D65-C0C0-0
SC31D75-C0C0-0
Unit Data Full function – C0C0
(1)
Nominal Run Amps
A
77.1
77.1
77.1
Maximum Start Amps
A
77.1
77.1
77.1
Recommended Mains Fuse Size
A
100
100
100
Max Mains Incoming Cable Size
mm²
35
35
35
Mains Supply
V
400V / 3PH + N / 50Hz
Control circuit
VAC
24
24
24
Unit Data Cooling Only – C0C0
Nominal Run Amps
A
15.4
15.4
15.4
Maximum Start Amps
A
15.4
15.4
15.4
Recommended Mains Fuse Size
A
25
25
25
Evaporator Fan - Motor - Per Fan
Motor Type
EC
EC
EC
Quantity x Motor Size
(2)
kW
3 x 3.1
3 x 3.1
3 x 3.1
Full Load Amps
A
4.8
4.8
4.8
Locked Rotor Amps
A
4.8
4.8
4.8
OPTIONAL EXTRAS
Electric Heating
Stage of Reheat
3
3
3
Number of Elements
9
9
9
Rating (Total)
kW
31.5
31.5
31.5
Current Per Phase
A
45.5
45.5
45.5
Humidifier
Capacity
kg/hr
15
15
15
Rating
kW
11.25
11.25
11.25
Full Load Amps
A
16.2
16.2
16.2
First upgrade Fan Motor - EC Motor - Per Fan
Quantity x Motor Size
kW
N/A
N/A
N/A
Full Load Amps
A
N/A
N/A
N/A
Locked Rotor Amps
A
N/A
N/A
N/A
Second upgrade Motor - EC Motor - Per Fan
Quantity x Motor Size
kW
N/A
N/A
N/A
Full Load Amps
A
N/A
N/A
N/A
Locked Rotor Amps
A
N/A
N/A
N/A
(1) Values given for function units with standard selections for heating, humidification, supply air fans.
(2) Stated motor power is based on maximum electrical power absorbed
C
0
C0