Smartcool, Precision air conditioning, Mechanical data- condensers and dry coolers – Airedale SmartCool 11-233kW User Manual
Page 210
SmartCool
TM
- D
Precision Air Conditioning
210
Precision Air Conditioning
Installation, Maintenance and Commissioning Manual :6877419 02/2013
Mechanical Data- Condensers and Dry Coolers
CR80
CR95
CR105
DR40
DR50
DR55
Total Heat of Rejection CR
(1)
kW
87.8
110.9
113.2
Total Heat of Rejection DR
(2)
kW
41.8
53
54.4
Dimensions - Horizontal
(3)
H x W x L
mm
1167 x 1000 x 3565
1167 x 1000 x 3565
1167 x 1000 x 3565
Dimensions - Vertical
(3)
H x W x L
mm
1090 x 1167 x 3565
1155 x 1167 x 3565
1090 x 1167 x 3565
Weight
Machine
kg
208
258
260
Construction
Material/Colour
Galvanised Sheet Steel, Epoxy Baked Powder Paint - Light Grey (RAL 7035)
Condenser
Air Cooled - Rifled Copper Tube/Turbulated Aluminium Fins
Dry Cooler
Air Cooled - Copper Tube/Turbulated Aluminium Fins
Total Face Area
m²
3.63
3.63
3.63
Nominal Airflow
m³/s
7.5
10.8
6.6
Discharge
-H Horizontal or -V Vertical (Please Specify at Order)
Fan & Motor
Axial
Quantity
3
3
3
Diameter
mm
630
710
630
Maximum Speed
rpm
895
930
895
Refrigeration - CR
Single Circuit
Refrigerant Type
R410A
Holding Charge
Inert Gas
Coil Volume
l
18.3
18.3
36.6
Refrigerant Charge
(4)
kg
8.4
8.4
16.7
Dry Cooler
Internal Water Volume
L
23.1
23.1
43.2
Water flowrate
l/s
2.0
2.5
2.6
Pressure Drop
kPa
48.5
70
32
Connections
Liquid Line - Sweat
in
7/8
7/8
7/8
Discharge Line - Sweat
in
1 3/8
1 3/8
1 3/8
OPTIONAL EXTRAS
Short Case Axial Fan
Designed to 75 Pa ESP
Dimensions - Horizontal
H x W x L
mm
1167 x 1000 x 3565
1167 x 1000 x 3565
1167 x 1000 x 3565
Dimensions - Vertical
H x W x L
mm
1130 x 1167 x 3565
1140 x 1167 x 3565
1130 x 1167 x 3565
Weight
Machine
kg
242
249
294
EC Fan
Dimensions - Horizontal
H x W x L
mm
1167 x 1000 x 3565
1167 x 1000 x 3565
1167 x 1000 x 3565
Dimensions - Vertical
H x W x L
mm
1127 x 1167 x 3565
1170 x 1167 x 3565
1127 x 1167 x 3565
Weight
Machine
kg
228
293
280
(1) Nominal data based on 35°C ambient and a 50°C mean condensing temperature and using standard fan.
(2) Nominal data based on 35°C ambient and a 45/40°C Water entering / leaving.
(3) Overall dimensions for clearance; refer to
Dimensional & Installation Data
, for detail.
(4) For guidance only.
O
U
T
D
OOR