IBM AA-RWF3A-TE User Manual
Page 111

CAUTION:
If the SFP you does not have a bale, use a small implement, such as a
screwdriver, to press and release the trigger beneath the port. Non-baled
SFPs can be damaged by the removal process and are not recommended.
See
SAN Swtich optional kits
on page 33 for a list of supported SFPs.
5.
Repeat this procedure for the remaining ports, as required.
To install a replacement SFP:
1.
Make sure that the bale is in the unlocked position, and then place the SFP in the
correctly oriented position on the port. See
.
NOTE:
Each SFP includes a 10-pad gold-plated PCB-edge connector on the
bottom. The correct position to insert an SFP into the upper row of ports is
with the gold edge down. The correct position to insert an SFP into the
lower row of ports is with the gold edge up.
2.
Slide the SFP into the port until you feel it click into place, and then close the bale.
SAN Switch installation guide
111