IV. ADJUSTMENT OF COMPONENTS

1. ADJUSTMENT OF WATER REGULATING VALVE - WATER-COOLED

MODEL ONLY

The Water Regulating Valve also called “WATER REGULATOR” is factory-adjusted. No
adjustment is required under normal use. Adjust the Water Regulator , if necessary, using
the following procedures.

1) Attach a pressure gauge to the high-side line of the system. Or prepare a thermometer

to check the condenser drain temperature.

2) Rotate the Adjustment Screw by using a flat blade screwdriver, so that the pressure

gauge shows 260 PSIG (R-404A models/-F type), or the thermometer reads 100 -104°F,
in 5 minutes after the icemaking process starts. When the pressure exceeds 260 PSIG,
or the condenser drain temperature exceeds 104°F, rotate the Adjustment Screw
counterclockwise.

3) Check that the pressure or the condenser drain temperature holds a stable setting.

Adjustment Screw

Adjustment Screw

Bottom View

CW - Higher

CCW - Lower

CW

CCW