2.5.3 Analog input boards
A universal Analog Input board accepts a variety of input signals from field devices.
Figure 2-1 illustrates the terminal block connections for the various inputs. One AI board can be
configured to accept multiple input types.
Table 2-1 Universal Analog Input Board Specifications
Specification
Description
Input Types
mV, V, mA, T/C, RTD, and Ohms
Number of Inputs
4 per board, up to 12 boards per video recorder (48 inputs)
Signal Source
Thermocouple with cold junction compensation, for operation
between 0 to 80º C (32 to 176º F)
Line resistance up to 1000 ohms, T/C, mV, mA, V
RTD, 3-wire connections, 40 ohms balanced max.
Input
Impedance
10 Meg
Ω for T/C, mV inputs,
> 1 Meg
Ω for volt inputs
+
-
T / C , m V , V
+
-
*
4 t o 2 0
m A
S o u r c e
1 2
1 1
1 0
9
8
7
6
5
4
3
2
1
1
C h a n n e l 4
C h a n n e l 3
C h a n n e l 2
C h a n n e l 1
+
-
+
-
+
-
R T D
+
-
R T D
T h e r m o c o u p l e i n p u t
G r o u n d T e r m i n a l
R T D I n p u t ( 3 w i r e s )
+
-
R T D
C u r r e n t I n p u t m A
* A 2 5 0 o h m r e s i s t o r i s r e q u i r e d f o r t h e
i n p u t r a n g e
G r o u n d T e r m i n a l
m V , V I n p u t s
+
-
m V o r V
s o u r c e
G r o u n d T e r m i n a l
G r o u n d T e r m i n a l
S l o t I D
Figure 2-1 AI Board Terminal Block Connections
Figure 2-2 10 ohm Copper connections
-
+
RTD
-
+
RTD
10 ohm Copper
with common ground lead
Grounded lead of
RTD should be
connected to RTD
terminal of VRX
terminal block
All RTD connections are
common on Universal AI
board.