Select a profile to edit. see table 5-5 for – Honeywell VRX180 User Manual
Page 207

Setpoint Profiler
Video Recorder – User Manual
193
Table 5-5 Edit Profile Prompts
Prompt
Range/Selections
Definition
RAMP TYPE
VAL/DUR, TIME, RATE,
EXTERNAL
See 4 types of ramp segments on page 178.
TIME UNITS
SECS, MINS, HOURS
Select the time units to be used by all segments
of the profile.
EDIT SEGMENTS
GUAR SOAK LO LIM
OFF or number
The profiler will Hold if PV #1 or PV #2 deviates
more than this much below the profiler output.
See Guaranteed Soak on page 182 for details.
GUAR SOAK HI LIM
OFF or number
The profiler will Hold if PV #1 or PV #2 deviates
more than this much above the profiler output.
See Guaranteed Soak on page 182 for details.
HYSTERESIS
OFF or number
See Hysteresis on page 182 for details.
BATCH FIRST
SEGMENT
0-63
Specify the first segment of the batch phase.
Prior segments are the start-up phase. A value
of 0 indicates a single phase profile. See Two
types of profiles on page 177 for details.
BATCH LAST
SEGMENT
0-63
Specify the last segment of the batch phase.
Segments after this segment are the shutdown
phase. A value of 0 indicates a single phase
profile. See Two types of profiles on page 177
for details.
(continued)